NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Orifice Sizes - Sea Level to High Altitude
(All Models):
These appliances are tested and

approved for installations at elevations of 0-4500

feet (0-1372 meters) above sea level using the

standard burner orifice sizes (marked with an

"*" in Table 4).
For higher elevations, contact your gas supplier

or qualified service technician.
Install the appliance according to the regulations

of the local authorities having jurisdiction and,

in the USA, the National Fuel Gas Code NFPA

54 / ANSI Z223.1 - latest edition or, in Canada,

the CAN/CSA-B149.1- latest edition.

Burner Orifice Sizes

Elevation 0-4500 feet ( 0-1372 meters)

Model

Nat.Gas

drill size (inches)

Propane

drill size (inches)

LSM40-2 0.1405" (#28)*

• H2286

0.086" (#44)*

• H2287

LSM45-2 0.161" (#20)*

• H2288

0.093" (#42)*

• H4816

Table 4

* Standard size installed at factory

• Part /Cat. Number

Deration
At higher elevations, the amount of BTU fuel

value delivered must be reduced by either using

gas that has been derated by the gas company

or by changing the burner orifice to a smaller

size as regulated by the local authorities having

jurisdiction and by the (USA) National Fuel Gas

Code NFPA 54/ANSI Z223.1 - latest edition or,

in Canada, the CAN/CSA-B149.1 codes - latest

edition.

Burn-in Period

During the first few fires of this appliance there

will be some odor due to the curing of the

paint and burning off of lubricants used in the

manufacturing process. Depending on your

use, the burn-in period may take a few hours

or a few days.
KEEP YOUR HOUSE WELL VENTILATED

DURING THE CURING PROCESS. THE ODOR

AND HAZE EMITTED DURING THE CURING

PROCESS CAN BE QUITE NOTICEABLE AND

MAY SET OFF A SMOKE DETECTOR.

Input (BTU/HR) - All Models

Natural Gas

Propane Gas

Model

No.

Input

(BTU/Hr)

Model

No.

Input

(BTU/Hr)

LSM40-2

40,000 to

50,000

LSM40-2 40,000 to

50,000

LSM45-2

47,000 to

60,000

LSM45-2 48,000 to

60,000

Table 1

Test gauge connections are provided on the

front of the millivolt and electronic gas control

valve, identified IN for the inlet and OUT for the

manifold side (see Figures 2 and 3 on Page 8).

The control valves have a 3/8" (10 mm) NPT

thread inlet and outlet side of the valve.

GENERAL INFORMATION

The fireplace models covered in this manual are

direct-vent, sealed combustion gas fireplaces

designed for residential application. Direct-

vent appliances operate with the combustion

chamber completely isolated from the indoor

environment.

All air for combustion is brought in from the

outside and exhaust gases are vented through

the same direct-vent, co-axial (intake/exhaust)

vent system.

The Millivolt appliances are designed to oper-

ate on either natural or propane gas and have

a millivolt gas control valve with piezo ignition

system.

The Electronic appliances are designed to oper-

ate on natural gas only and contain an electronic

intermittent pilot system. External electrical

power is required to operate these units.

These appliances comply with National Safety

Standards and are tested and listed by OMNI-

Test Laboratories, Inc. (Report No. 116-F-22-5)

to ANSI Z21.50 (in Canada, CSA-2.22), and CAN/

CGA-2.17-M91 in both the USA and Canada as

vented gas fireplaces.

The Installation must conform to local codes or,

in the absence of local codes, with the National

Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest

edition, or the Natural Gas and Propane Instal-

lation Code, CSA B149.1 - latest edition. The

appliance, when installed, must be electrically

grounded in accordance with local codes or, in

the absence of local codes, with the National

Electrical Code, ANSI/NFPA 70 - latest edition,

or the Canadian Electrical Code, CSA C22.1 -

latest edition.

NOTICE:

A white film may develop

on the glass enclosure panel during

the first few fires as part of the burn-in

process.
The first few times you use the

fireplace, clean the glass after each use

(AFTER THE GLASS HAS COMPLETELY

COOLED); otherwise, the white film

will bake onto the glass and become

difficult to remove.
See glass cleaning instructions on

Page 9.

LENNOX HEARTH PRODUCTS • MONTEBELLO

®

DV GAS FIREPLACES

(LSM40/45MN-2, LSM40/45MP-2, LSM40/45EN-2)

• CARE AND OPERATION INSTRUCTIONS

BTU Input
Millivolt and electronic models come standard

with a manually-modulated gas valve; flame

appearance and heat output can be controlled

at the gas valve. The BTU Input for these ap-

pliances are shown in Table 1.

Gas Pressure

Tables 2 and 3 show the appliances' gas pres-

sure requirements.

Inlet Gas Supply Pressure

(all models)

Fuel #

Minimum

Maximum

Natural Gas

5.5" WC

(1.37 kPa)

10.5" WC

(2.61 kPa)

Propane

11.0" WC

(2.74 kPa)

13.0" WC

(3.23 kPa)

Table 2

Manifold Gas Supply Pressure

(all models)

Fuel #

Low

High

Natural

Gas

(Lo) 2.2" WC

(0.55 kPa)

(Hi) 3.5" WC

(0.87 kPa)

Propane (Lo) 6.3" WC

(1.57 kPa)

(Hi) 10.0" WC

(2.49 kPa)

Table 3

These appliances must be isolated from
the gas supply piping system (by closing
their individual manual shut-off valve)
during any pressure testing of the gas
supply piping system at test pressures
equal to or less than 1/2 psig (3.5 kPa).

These appliances and their individual
shut-off valves must be disconnected
from the gas supply piping system dur-
ing any pressure testing of that system
at pressures greater than 1/2 psig (3.5
kPa).