Lennox Hearth ELITE 875022M User Manual

Page 7

Advertising
background image

7

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

BTU Input

These fireplaces are designed as supplemental

heaters. Therefore, it is advisable to have an

alternate primary heat source when installed

in a dwelling.

Millivolt Models - The millivolt appliances are

manually controlled and feature a spark igniter

(piezo) that allows the appliance's pilot gas to

be lit without the use of matches or batteries.

This system provides continued service in the

event of a power outage.

Millivolt models come standard with a manually-

modulated gas valve; flame appearance and

heat output can be controlled at the gas valve.

The BTU Input for these appliances is shown

in Table 1.

Electronic Models - Electronic models have a

fixed rate gas valve. Input of electronic models

is shown in Table 1.

Burn-in Period

During the first few fires of this appliance there

will be some odor due to the curing of the

paint and burning off of lubricants used in the

manufacturing process. Depending on your

use, the burn-in period may take a few hours

or a few days.

KEEP YOUR HOUSE WELL VENTILATED

DURING THE CURING PROCESS. THE ODOR

AND HAZE EMITTED DURING THE CURING

PROCESS CAN BE QUITE NOTICEABLE AND

MAY SET OFF A SMOKE DETECTOR.

If an optional blower is installed, Do Not turn

it on during the Burn-In period.

A white film may develop on the glass front

during the first few fires as part of the curing

process. The glass should be kept clean during

the first two weeks of use to prevent the film from

baking on (making it very difficult to remove).

See Cleaning Glass on Page 10.

Test gauge connections are provided on the

front of the millivolt and electronic gas control

valve (identified IN for the inlet and OUT for the

manifold side). The control valves have a 3/8"

(10mm) NPT thread inlet and outlet side of the

valve (refer to Figures 1 and 2).

Propane tanks are at pressures that will cause

damage to valve components. Verify that the

tanks have step down regulators to reduce the

pressure to safe levels.

These appliances must not be connected to a

chimney or flue serving a separate solid fuel

burning appliance.

Orifice Sizes - Sea Level to High Altitude

(All Models)

These appliances are tested and approved for

installation at elevations of 0-4500 feet (0-1372

meters) above sea level using the standard burner

orifice sizes (marked with an "*" in Table 4 ).

For elevations above 4500 feet, contact your gas

supplier or qualified service technician.

Manifold Gas Supply Pressure

(all models)

Fuel #

Low

High

Natural

Gas

(Lo) 2.2" WC

(0.55 kPa)

(Hi) 3.5" WC

(0.87 kPa)

Propane (Lo) 6.3" WC

(1.57 kPa)

(Hi) 10.0" WC

(2.49 kPa)

Table 3

These appliances must be isolated from the

gas supply piping system (by closing their

individual manual shut-off valve) during any

pressure testing of the gas supply piping

system at test pressures equal to or less

than 1/2 psig (3.5 kPa).

These appliances and their individual shut-off

valves must be disconnected from the gas

supply piping system during any pressure

testing of that system at pressures greater

than 1/2 psig (3.5 kPa).

Inlet Gas Supply Pressure

(all models)

Fuel #

Minimum

Maximum

Natural Gas

4.5" WC

(1.12 kPa)

10.5" WC

(2.61 kPa)

Propane

11.0" WC

(2.74 kPa)

13.0" WC

(3.23 kPa)

Table 2

Gas Pressure - All Models
Tables 2 and 3
show the appliances' inlet and

manifold gas pressure requirements:

Deration - At higher elevations, the amount

of BTU fuel value delivered must be reduced

by either using gas that has been derated by

the gas company or by changing the burner

orifice to a smaller size as regulated by the

local authorities having jurisdiction and by the

(USA) National Fuel Gas Code NFPA 54/ANSI

Z223.1 - latest edition or, in Canada, the CAN/

CSA-B149.1 codes - latest edition.

Install the appliance according to the regulations

of the local authorities having jurisdiction and,

in the USA, the National Fuel Gas Code NFPA

54 / ANSI Z223.1 - latest edition or, in Canada,

the CAN/CSA-B149.1 - latest edition.

Flame breadth, height and width will dimenish

4% for every 1,000 feet of altitude.

Burner Orifice Sizes (all models)

Elevation

Feet (meters)

Natural

Gas

drill size (inches)

Propane

Gas

drill size (inches)

0-4500

(0-1372)

(0.125")

*

21L81 •

#41 (0.096")

*

21L82 •

Table 4

* Standard size installed at factory

• Part /Cat. Number

Input (BTU) Gas Valves (all models)

All Models

Fuel

Type

Input Rate

(BTU / HR)

Millivolt

Natural

39,000 high

31,000 low

Millivolt

(if field converted)

Propane 39,000 high

31,000 low

Electronic

Natural

39,000

Electronic

(if field converted)

Propane

39,000

Table 1