Electrical Installation

6

Top Cable Entry

When making the power connections, the recommended order of pulling and installing cables

is to start from the top connections to the bottom connections. The cables must be routed

around the fault braces (see Detail in Figure 3). This is to prevent the cables from contacting

other busbars. The recommended conduit layout is shown in Figure 1.

Bottom Cable Entry

When making the power connections, the recommended order of pulling and installing cables

is to start from the bottom connections to the top connections. The cables must be routed

around the fault braces (see Detail in Figure 3. This is to prevent the cables from contacting

other busbars. The recommended conduit layout is shown in Figure 1.

5. Close and secure the interior and exterior doors.

NOTE
For a Single Input configuration, linking busbars must be installed between the bypass and

the rectifier input.

!

WARNING

Risk of electrical shock. Can cause injury or death.
If the load equipment will not be ready to accept power on the arrival of the commissioning

engineer, ensure that the system output cables are safely isolated at their termination.

!

WARNING

Risk of electrical shock. Can cause injury or death.
When connecting the cables between the battery extremities to the circuit breaker always

connect the circuit breaker end of the cable first.

NOTE
If fault bracing brackets were removed during installation, they MUST be replaced.

Table 1

Current ratings—rectifier input

UPS Rating

Voltage, VAC

Nominal

Current

Maximum

Current

External

100% Breaker

Trip, Amps

External

80% Breaker

Trip, Amps

kVA

kW

Input

Bypass

Output

250

225

480

480

480

313

392

400

500

300

270

480

480

480

376

469

500

600

400

360

480

480

480

500

625

700

800

Table 2

Current ratings—bypass input

UPS Rating

Voltage, VAC

Nominal

Current

10 Minute

Overload

External Breaker

Trip, Amps

kVA

kW

Input

Bypass

Output

250

225

480

480

480

301

376

400

300

270

480

480

480

361

451

500

400

360

480

480

480

481

601

700

Table 3

Current ratings—output

UPS Rating

Voltage, VAC

Nominal

Current

10 Minute

Overload

External Breaker

Trip, Amps

kVA

kW

Input

Bypass

Output

250

225

480

480

480

301

376

400

300

270

480

480

480

361

451

500

400

360

480

480

480

481

601

700