Table 4 current ratings—battery, Notes on tables, Table 5 recommended conduit and cable sizes – Liebert Ship-Ahead Input/Output Cabinet NXL User Manual

Page 11: Table 4, Current ratings—battery, Table 5, Recommended conduit and cable sizes, H 4 for ov

Advertising
background image

Electrical Installation

7

Notes on Tables

1. Nominal input current (considered continuous) is based on full-rated output load. Maximum

current includes nominal input current and maximum battery recharge current (considered

noncontinuous). Continuous and noncontinuous current are defined in NEC 100. Maximum input

current is controlled by the current limit setting which is adjustable. Values shown are for

maximum setting of 125%. Standard factory setting is 125%.

2. Recommended bypass external overcurrent protection is based on 125% overload capacity for 10

minutes.

3. All recommended external overcurrent protections are based on 80% rated breakers.
4. Nominal battery voltage is shown at 2.0 volts / cell.

Table 4

Current ratings—battery

UPS Rating

Nominal VDC

Maximum Battery

Current at EOD

External Breaker

Trip, Amps

kVA

kW

250

225

480

615

700

300

270

480

737

800

400

360

480

981

1000

Table 5

Recommended conduit and cable sizes

Rectifier Input

UPS Rating

Voltage

(VAC)

Nominal Selection

Alternate Selection

Top Cable Entry Input

Wire & Conduit

Ph, G THW / FMC

Bottom Cable Entry

Input Wire & Conduit

Ph, G THW / RNC

Top Cable Entry Input

Wire & Conduit

Ph, G THW / FMC

Bottom Cable Entry

Input Wire & Conduit

Ph, G THW / RNC

kVA

kW

Input

Bypass

Output

250

225

480

480

480

(2) 2.5C 3-250kcmil,

#1/0AWG

(2) 2.5C 3-250kcmil,

#1/0AWG

(3) 2C 3-#2/0AWG,

#1/0AWG

(3) 2C 3-#2/0AWG,

#1/0AWG

300

270

480

480

480

(2) 3C 3-350kcmil,

#1/0AWG

(2) 3C 3-350kcmil,

#1/0AWG

(3) 2.5C 3-#4/0AWG,

#1/0AWG

(3) 2.5C 3-#4/0AWG,

#1/0AWG

400

360

480

480

480

(2) 3C 3-500kcmil,

#1/0AWG

(2) 3.5C 3-500kcmil,

#1/0AWG

(3) 2.5C 3-250kcmil,

#1/0AWG

(3) 2.5C 3-250kcmil,

#1/0AWG

Bypass Input

UPS Rating

Voltage (VAC)

Nominal Selection

Alternate Selection

Top Cable Entry Input

Wire & Conduit

Ph, N, G THW / FMC

Bottom Cable Entry

Input Wire & Conduit

Ph, N, G THW / RNC

Top Cable Entry Input

Wire & Conduit

Ph, N, G THW / FMC

Bottom Cable Entry

Input Wire & Conduit

Ph, N, G THW / RNC

kVA

kW

Input

Bypass

Output

250

225

480

480

480

(3) 2.5C 3-#2/0AWG,

2-#1/0AWG, #1/0AWG

(3) 3C 3-#2/0AWG,

2-#1/0AWG, #1/0AWG

(2) 3C 3-250kcmil,

2-#4/0AWG, #1/0AWG

(2) 3C 3-250kcmil,

2-#4/0AWG, #1/0AWG

300

270

480

480

480

(3) 2.5C 3-#4/0AWG,

2-#1/0AWG, #1/0AWG

(3) 3C 3-#4/0AWG,

2-#1/0AWG, #1/0AWG

(2) 3C 3-350kcmil,

2-#4/0AWG, #1/0AWG

(2) 3.5C 3-350kcmil,

2-#4/0AWG, #1/0AWG

400

360

480

480

480

(3) 3C 3-250kcmil,

2-#4/0AWG, #1/0AWG

(3) 3C 3-250kcmil,

2-#4/0AWG, #1/0AWG

(2) 3.5C 3-500kcmil,

2-350kcmil, #1/0AWG

(2) 4C 3-500kcmil,

2-350kcmil, #1/0AWG

Output

UPS Rating

Voltage (VAC)

Nominal Selection

Alternate Selection

Top Cable Entry Input

Wire & Conduit

Ph, N, G THW / FMC

Bottom Cable Entry Input

Wire & Conduit

Ph, N, G THW / RNC

Top Cable Entry Input

Wire & Conduit

Ph, N, G THW / FMC

Bottom Cable Entry

Input Wire & Conduit

Ph, N, G THW / RNC

kVA

kW

Input

Bypass

Output

250

225

480

480

480

(3) 2.5C 3-#2/0AWG,

2-#1/0AWG, #1/0AWG

(3) 3C 3-#2/0AWG,

2-#1/0AWG, #1/0AWG

(3) 2.5C 3-#2/0AWG,

2-#1/0AWG, #1/0AWG

(3) 3C 3-#2/0AWG,

2-#1/0AWG, #1/0AWG

300

270

480

480

480

(3) 2.5C 3-#4/0AWG,

2-#1/0AWG, #1/0AWG

(3) 3C 3-#4/0AWG,

2-#1/0AWG, #1/0AWG

(3) 2.5C 3-#4/0AWG,

2-#1/0AWG, #1/0AWG

(3) 3C 3-#4/0AWG,

2-#1/0AWG, #1/0AWG

400

360

480

480

480

(3) 3C 3-250kcmil,

2-#4/0AWG, #1/0AWG

(3) 3C 3-250kcmil,

2-#4/0AWG, #1/0AWG

(3) 3C 3-250kcmil,

2-#4/0AWG, #1/0AWG

(3) 3C 3-250kcmil,

2-#4/0AWG, #1/0AWG

Battery

UPS Rating

Voltage (VAC)

Nominal Selection

Alternate Selection

Top Cable Entry Input

Wire & Conduit

Wires, G THW / FMC

Bottom Cable Entry Input

Wire & Conduit

Wires, G THW / RNC

Top Cable Entry Input

Wire & Conduit

Wires, G THW / FMC

Bottom Cable Entry Input

Wire & Conduit

Wires, G THW / RNC

kVA

kW

Input

Bypass

Output

250

225

480

480

480

(2) 2.5C 2-350kcmil,

#1/0AWG

(2) 2.5C 2-350kcmil,

#1/0AWG

(3) 2C 2-#4/0AWG,

#1/0AWG

(3) 2C 2-#4/0AWG,

#1/0AWG

300

270

480

480

480

(2) 2.5C 2-500kcmil,

#1/0AWG

(2) 3C 2-500kcmil,

#1/0AWG

(3) 2C 2-250kcmil,

#1/0AWG

(3) 2C 2-250kcmil,

#1/0AWG

400

360

480

480

480

(3) 2.5C 2-500kcmil,

#4/0AWG

(3) 3C 2-500kcmil,

#4/0AWG

(4) 2C 2-250kcmil,

#4/0AWG

(4) 2.5C 2-250kcmil,

#4/0AWG

If the UPS is used in a four-wire system, the neutral ground jumper must be removed.