SERIES B-VENT GAS FIREPLACES • 42" LMBV MODELS • INSTALLATION INSTRUCTIONS

Figure 12

Figure 13

b. electronic Wiring

The electronic appliance must be connected to

the main power supply. To install:

1. Route a 3-wire 120V 60Hz power supply

to the appliance junction box and ground.

(See Figures 13 and 14 ).

2. Locate and install a low voltage (24V)

wall switch (not supplied) in the desired

location. Connect the low voltage wire to

this switch (see Figure 13).

3. After wiring is complete, replace the ap-

pliance junction box cover and secure with

the hex head screws previously removed.

Step 5. Field Wiring; Install Optional

Wall Switch

Refer to Section A, below, for millivolt appliances

and Section B, below, for electronic appliances.

A. millivolt Wiring

The gas valve has been set in place and has

been pre-wired at the factory. No additional

wiring is required unless the optional wall

switch or optional remote control kit is to be

installed. Locate the optional wall switch or

optional remote control in the desired location

and connect the millivolt wire (see Figure 12).

CAUTION: DO NOT CONNeCT THe WALL

SWITCH TO A 120v pOWeR SUppLY.

NOTE: Optional wall switch not supplied. If the

optional wall switch is not installed, the ends of

the 15' coiled wire must be connected with a wire

nut (not supplied) for the appliance to operate.

MILLIVOLT WIRING DIAGRAM

NOTE: If any supplied wire must be replaced,

always use Type AWM, 105°C, 18 GA wire.

BK

BK

BK

TP
TH

BK

WHT

LIMIT

SWITCH

THERMOPILE

*

FACTORY WIRED
FIELD WIRED

*

For optional wall switch attachment only.

DAMPER

SWITCH

TP

TH

* Control Switches: Wall On/Off Switch or Timer, Unit Mounted On/Off Switch, or Remote Control Switch. If an optional

control switch is installed, turn the appliance-mounted ON/OFF burner control switch to the OFF position.

NOTES:

1. If any of the original wire as supplied must be replaced, use Type AWM 105°C - 18 gage wire ONLY.

2. 120 VAC, 60 Hz - Less than 3 Amps.

CAUTION: label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and

dangerous operation. Verify proper operation after servicing.

CAUTION

Ground supply lead must be con-

nected to the wire attached to the

green ground screw located on the

outlet box. See

Figure 14

. Failure to

do so will result in a potential safety

hazard. The appliance must be

electrically grounded in accordance

with local codes or, in the absence of

local codes, the National electrical

Code, ANSI/NFpA 70-latest edition.

(In Canada, the current CSA C22.1

Canadian Electrical Code).

0.375"

0.375"

0.25" Ø

NOT FOR USE WITH SOLID FUEL

CAUTION:

Hot while in operation. Do not

touch. Severe Burns may result. Keep children, clothing,

furniture, gasoline and other liquids having flammable

vapors away.

CAUTION:

Do not operate the appliance with

factory installed refractory panel(s) removed, cracked or

broken. Replacement of the factory installed refractory

panel(s) should be completed by a licensed or qualified

service person.

WARNING:

Improper installation, adjustment,

alteration, service or maintenance can cause injury

or property damage. Refer to the owner’s information

manual provided with this appliance. For assistance

or additional information consult a qualified installer,

service agency or the gas supplier.
Due to high temperatures, keep children, and furniture

away.
Keep burner and control compartment clean. See

installation and operating instructions accompanying

appliance.

WARNING:

Do not connect 120 V AC to the control valve.

THIS APPLIANCE MUST BE INSTALLED IN ACCORDANCE

WITH LOCAL CODES, IF ANY; IF NONE, FOLLOW THE

NATIONAL FUEL GAS CODE, ANSI Z223.1, OR NATURAL

GAS AND PROPANE INSTALLATION CODE, CSA B149.1.

If not installed, and maintained in accordance with the

manufacturer's instructions, this product could expose

you to substances in fuel or fuel combustion which are

known to the state of California to cause cancer, birth

defects, or other reproductive harm.

* For a copy of the homeowner’s care and operation

manual, go to www.lennox.com or call 1-800-9-lennox.

B-VENTED APPLIANCES NEED FRESH AIR FOR SAFE

OPERATION AND MUST BE INSTALLED SO THERE

ARE PROVISIONS FOR ADEQUATE COMBUSTION AND

VENTILATION AIR.

DIRECT VENTED APPLIANCES MUST NOT BE OPERATED

WITHOUT THE FRONT GLASS PANEL(S) INSTALLED.

DO NOT OPERATE APPLIANCE WITH BROKEN,

CRACKED OR MISSING GLASS DOORS OR ENCLOSURE

PANEL(S).

ELECTRONIC IGNITION WIRING DIAGRAM

P/N 62L2701_4

Optional Blower**

OFF/ON Switch

(Integral with

Gas Valve)

Honeywell

Electronic

Gas

Valve

120 VAC

Primary

Secondary

Junction Box

Break Off Tab

Junction Box

Pilot Burner

Assembly

BL

BL

Field Wired
Factory

Wired

BK = BLACK BL = BLUE

R = RED W = WHITE

G = GREEN

BK

BK

BK

BK

BL

R

GROUND

24 V

Transformer

J-Box Wiring

WITH Optional Blower Switch

J-Box Wiring

WITHOUT Optional Blower Switch

BK

W

G

CA

V

02

1

BK

W

G

CA

V

02

1

Igniter

Connector

*

**

Control Switches: Wall On/Off

Switch, Unit Mounted On/Off Switch,

Wall Thermostat (Direct-Vent Units

Only) or Remote Control Switch.

Some models are not approved for

use with an optional blower. See Care

and Operation manual for approved

accessories.

Schematic Representation Only

W

GR

BK

BK

R

Control

Switch *

DAMPER

SWITCH

HIGH LIMIT

SWITCH

B-Vent appliances only - one or both of these switches must

be factory installed in series as shown. If wires to these switches

are replaced, wires must be Type AWM 200°C - 18 gage wire ONLY.

NOTES:

1. If any of the original wire as supplied

must be replaced, use Type AWM

105°C - 18 gage wire ONLY.

2. 120 VAC, 60 Hz - Less than 3 Amps.

CAUTION: label all wires prior to

disconnection when servicing controls.

Wiring errors can cause improper and

dangerous operation. Verify proper

operation after servicing.

0.375"

0.375"

0.25" Ø

NOT FOR USE WITH SOLID FUEL

CAUTION:

Hot while in operation. Do not

touch. Severe Burns may result. Keep children, clothing,

furniture, gasoline and other liquids having flammable

vapors away.

CAUTION:

Do not operate the appliance with

factory installed refractory panel(s) removed, cracked or

broken. Replacement of the factory installed refractory

panel(s) should be completed by a licensed or qualified

service person.

WARNING:

Improper installation, adjustment,

alteration, service or maintenance can cause injury

or property damage. Refer to the owner’s information

manual provided with this appliance. For assistance

or additional information consult a qualified installer,

service agency or the gas supplier.
Due to high temperatures, keep children, and furniture

away.
Keep burner and control compartment clean. See

installation and operating instructions accompanying

appliance.

WARNING:

Do not connect 120 V AC to the control valve.

THIS APPLIANCE MUST BE INSTALLED IN ACCORDANCE

WITH LOCAL CODES, IF ANY; IF NONE, FOLLOW THE

NATIONAL FUEL GAS CODE, ANSI Z223.1, OR NATURAL

GAS AND PROPANE INSTALLATION CODE, CSA B149.1.

If not installed, and maintained in accordance with the

manufacturer's instructions, this product could expose

you to substances in fuel or fuel combustion which are

known to the state of California to cause cancer, birth

defects, or other reproductive harm.

* For a copy of the homeowner’s care and operation

manual, go to www.lennox.com or call 1-800-9-lennox.

B-VENTED APPLIANCES NEED FRESH AIR FOR SAFE

OPERATION AND MUST BE INSTALLED SO THERE

ARE PROVISIONS FOR ADEQUATE COMBUSTION AND

VENTILATION AIR.

DIRECT VENTED APPLIANCES MUST NOT BE OPERATED

WITHOUT THE FRONT GLASS PANEL(S) INSTALLED.

DO NOT OPERATE APPLIANCE WITH BROKEN,

CRACKED OR MISSING GLASS DOORS OR ENCLOSURE

PANEL(S).

ELECTRONIC IGNITION WIRING DIAGRAM

P/N 62L2701_4

Optional Blower**

OFF/ON Switch

(Integral with

Gas Valve)

Honeywell

Electronic

Gas

Valve

120 VAC

Primary

Secondary

Junction Box

Break Off Tab

Junction Box

Pilot Burner

Assembly

BL

BL

Field Wired
Factory

Wired

BK = BLACK BL = BLUE

R = RED W = WHITE

G = GREEN

BK

BK

BK

BK

BL

R

GROUND

24 V

Transformer

J-Box Wiring

WITH Optional Blower Switch

J-Box Wiring

WITHOUT Optional Blower Switch

BK

W

G

CA

V

02

1

BK

W

G

CA

V

02

1

Igniter

Connector

*

**

Control Switches: Wall On/Off

Switch, Unit Mounted On/Off Switch,

Wall Thermostat (Direct-Vent Units

Only) or Remote Control Switch.

Some models are not approved for

use with an optional blower. See Care

and Operation manual for approved

accessories.

Schematic Representation Only

W

GR

BK

BK

R

Control

Switch *

DAMPER

SWITCH

HIGH LIMIT

SWITCH

B-Vent appliances only - one or both of these switches must

be factory installed in series as shown. If wires to these switches

are replaced, wires must be Type AWM 200°C - 18 gage wire ONLY.

NOTES:

1. If any of the original wire as supplied

must be replaced, use Type AWM

105°C - 18 gage wire ONLY.

2. 120 VAC, 60 Hz - Less than 3 Amps.

CAUTION: label all wires prior to

disconnection when servicing controls.

Wiring errors can cause improper and

dangerous operation. Verify proper

operation after servicing.

J-box Wiring

eLeCTRONIC IGNITION WIRING DIAGRAm