6

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

LENNOX HEARTH PRODUCTS • MERIT

®

SERIES B-VENT GAS FIREPLACES • 42" LMBV MODELS • INSTALLATION INSTRUCTIONS

CLeARANCeS

Minimum clearance to combustibles for the

appliance is as follows: sides and back - 0" (0

mm), floor - 0" (0 mm), adjacent wall - 0" (0

mm), ceiling - 64" (1625 mm). Service Clear-

ances, Front - 3' (0.9 m).

NOTE: 3" (75 mm) minimum clearance is

required above any inclined vent component.

1" minimum clearance is required to the sides

of vertical vent.

Hearth extension

- A hearth extension is not

required with this appliance. If a hearth exten-

sion is used, do not block the lower control

compartment door. Any hearth extension used

is for appearance only and does not have to

conform to standard hearth extension instal-

lation requirements.

Wall Finishes / Surrounds / mantels

NOTE: Combustible wall finish materials and/

or surround materials must not be allowed to

encroach the area defined by the appliance

front face (black sheet metal). Never allow

combustible materials to be positioned in

front of or overlapping the appliance face.

Non-combustible materials, such as surrounds

and other appliance trim, may be installed on

the appliance face with these exceptions: they

must not cover any portion of the removable

glass panel or control compartment.

Vertical installation clearances to combustible

mantels vary according to the depth of the

mantel. See Figure 6. Mantels constructed of

non-combustible materials may be installed

at any height above the appliance opening;

however, do not allow anything to hang below

the fireplace hood.

Minimum clearance requirements include any

projections such as shelves, window sills,

mantels, etc. above the appliance.

NOTE: We recommend the use of high tem-

perature paint (rated 175° F or higher) on the

underside of the mantel.

Wall Details and Combustible mantels -

Complete finished interior wall. To install the

appliance facing flush with the finished wall,

position framework to accommodate the

thickness of the finished wall (Figure 6). This

Figure also indicates vertical installation clear-

ances to combustible mantels. Figure 7 also

shows an example of a combustible mantel

shelf projecting a maximum of 12" (305 mm)

from the wall, and which must be installed a

minimum distance of 14-1/2" (368 mm) from

the top of the firebox opening.

Figure 6

Figure 7

Fireplace

Opening

Spacer

Finished

Wall

Header

1

2

3

4

5

6

7

8

9

10

11

12

9

10

11

12

Combustible Mantel Clearances

Inches

Min. Height of Mantel

Above Fireplace

Opening

Max.Length of Mantels

Three mantels are shown (dark gray elongated rectangles)-

one, 1-1/2 in. long at a min. of 8-3/8 in. above the fireplace opening;

the second, 8 in. long at a min. of 12 in. above the fireplace opening;

the third, 12 in. long at a min. of 14-1/4 in. above the fireplace opening;

for any mantels between these three in length, they must be located

within the lighter gray shaded area.

0

0

8-3/8

1-1/2

8

13

14

14-1/4

64"

(1626 mm)

Min. to

Ceiling

14-1/2" Min.

(368 mm)

0" (0 mm) Clearance

to Combustible

Side Wall

Max. Projection 12" (305 mm)

Combustible

Mantel