Refer to Figure 5.

3.1

Mimic Panel

The Mimic panel consists of the following:

• UPS SYSTEM 1 - PRIMARY BYPASS
• UPS SYSTEM 2 - PRlMARY BYPASS
• UPS SYSTEM 1 - ON BYPASS
• UPS SYSTEM 2 - ON BYPASS
• LOAD 1 CIRCUIT BREAKER
• LOAD 2 CIRCUIT BREAKER
• TIE CIRCUIT BREAKER

• LOAD 1 - NORMAL
• LOAD 1 - ON SYSTEM 2
• LOAD 1 - SYSTEMS TIED
• LOAD 1 - OFF

• LOAD 2 - NORMAL
• LOAD 2 - ON SYSTEM 1
• LOAD 2 - SYSTEMS TIED
• LOAD 2 - OFF

• CONTROL STATUS - SYNCHRONIZING
• CONTROL STATUS - TRANSFERRING

UPS System 1 - Primary Bypass

This light turns on when UPS System 1 is the selected Primary Bypass. When lit, the light indicates

the UPS Modules of both UPS systems are synchronizing to the bypass of UPS System 1, when sys-

tems are tied or in the process of transferring load.

UPS System 2 - Primary Bypass

This light turns on when UPS System 2 is the selected Primary Bypass. When lit, the light indicates

that the UPS Modules of both UPS systems are synchronizing to the bypass of UPS System 2, when

systems are tied or in the process of transferring load.

UPS System 1 - On Bypass

This light turns on when UPS System 1 is on Bypass.

UPS System 2 - On Bypass

This light turns on when UPS System 2 is on bypass.

Load 1 Circuit Breaker

These two lights indicate the OPEN (Red light) or CLOSED (Green light) state of the Load 1 circuit

breaker.

Load 2 Circuit Breaker

These two lights indicate the OPEN (Red light) or CLOSED (Green light) state of the Load 2 circuit

breaker.