Tie circuit breaker, Load 1 - normal, Load 1 - on system 2 – Liebert Series 610 User Manual

Page 25: Load 1 - systems tied, Load 1 - off, Load 2 - normal, Load 2 - on system 1, Load 2 - systems tied, Load 2 - off, Control status - synchronizing

Advertising
background image

Control Panel Description

21

Tie Circuit Breaker

These two lights indicate the OPEN (Red light) or CLOSED (Green light) state of the Tie circuit

breaker.

Load 1 - Normal

This light indicates that Load 1 is being supplied by UPS System 1. Load 1 supplied by UPS system 1

represents the normal operating mode.

Load 1 - On System 2

This light indicates that Load 1 is being supplied by UPS System 2 through the Tie circuit breaker.

Load 1 - Systems Tied

This light indicates that Load 1 is being supplied by both UPS Systems which share the combined

loads.

Load 1 - Off

This light indicates that Load 1 is isolated from both UPS Systems.

Load 2 - Normal

This light indicates that Load 2 is being supplied by UPS System 2. Load 2 supplied by UPS system 2

represents the normal operating mode

Load 2 - On System 1

This light indicates that Load 2 is being supplied by UPS System 1 through the Tie circuit breaker.

Load 2 - Systems Tied

This light indicates that Load 2 is being supplied by both UPS Systems which share the combined

loads.

Load 2 - Off

This light indicates that Load 2 is isolated from both UPS Systems.

Control Status - Synchronizing

This light indicates that the UPS Systems are currently synchronizing to the selected bypass line.

Control Status - Transferring

This light indicates that the controls are transferring a load from one system to the other system.

3.2

Load Transfer Controls

This section of the control panel gives indications and allows control of load transfers between the

UPS Systems.

OK to Transfer Load 1 to System 1

This light indicates that it is safe to transfer Load 1 from UPS System 2 to UPS System 1. The trans-

fer occurs when the PUSH TO TRANSFER AFTER OK button is pressed, but only if this light is on.

OK to Transfer Load 1 to System 2

This light indicates that it is safe to transfer Load 1 from UPS System 1 to UPS System 2. The trans-

fer occurs when the PUSH TO TRANSFER AFTER OK button is pressed, but only if this light is on.

OK to Transfer Load 2 to System 1

This light indicates that it is safe to transfer Load 2 from UPS System 2 to UPS System 1. The trans-

fer occurs when the PUSH TO TRANSFER AFTER OK button is pressed, but only if this light is on.

Advertising