Figure 16

Rain Cap

Flashing Collar

Flashing

Firestop

68” Min.

MM

39” Min.

MM

Non-Combustible

Facing

Roof Support

Attic Radiation Shield

The duct system must be installed respecting

the following:

1. Remove the plates closing up the 8” dia.

holes on top of the fireplace. Then, cut

the insulation in order to obtain two 8” dia.

openings. Fix the adaptors on the fireplace

openings by turning clockwise (Figures 14

and 15).

2. Maintain at least a 2” (50 mm) clearance

between the ducts and any combustible

material; the required hole size is 13” x 13”

(330 mm x 330 mm).

Exception #1: For the grills, the fram-

ing can be 10-3/4” x 10-3/4” (275 mm

X  MM TO PROVIDE THE CLEARANCE AS

REQUIRED BY THE INTEGRAL SPACERS ON THE

double outlet duct system.

3. The maximum number of elbows in a run of

duct is two.

 -AINTAIN AT LEAST  v  MM CLEARANCE

from the outlet grill framing to a combustible

ceiling, side wall, mantel or floor.

5. When traversing a combustible wall or floor,

a firestop must be installed at the wall or floor

penetration. The hole size must be 13” x 13”

(330 mm x 330 mm)

6. Do not connect the hot air ducts to a central

heating system. Malfunction of the heating

system’s blower will cause the fireplace to

overheat. A furnace duct is only single wall

and not double wall as is required for the

Ladera™ fireplace hot air exhaust.

 5SE ONLY )(0 GRILLS AND COMPONENTS AS

described in this manual. Other grills or

registers, for example, may be too restrictive

and may overheat the fireplace or ceiling.

8. Do not use insulated flexible ducts as they

will overheat.

9. Do not use tees or any other components

than the ones specifically listed here.

10. Never allow the ducting to pitch down as

hot air will be trapped creating a fire hazard.

Never route the ducting downwards.

11. The hot air outlet grills must be installed with

the louvers pointing downwards in order to

prevent overheating adjacent ceilings.

6-1/2” Min.

MM TO CEILING

X

Combustibles are not allowed below top spacers

above the fireplace. Facing in front of fireplace must

be non-combustible below this area.

X

./4% $)!'2!-3  ),,5342!4)/.3 !2% ./4 4/ 3#!,%

12

Central Forced Air Kit

NOTE: Not tested under EPA certification. If

installed, this appliance no longer qualifies

for EPA certification.

The knock-outs provided on the back and on

the sides of the Ladera™ fireplace allow the

connection of insulated flexible pipe which

enables you to heat adjacent rooms up to 50

feet from the fireplace hot air outlet.

The ducting system must be installed as de-

scribed below:

A) Remove knock-out plate and cut insulation

THE ADAPTOR AT THE BACK ANDOR THE SIDE OF THE

fireplace. Fix the adaptor by twist-locking it

to the fireplace. You can use more than one

outlet on the fireplace (see Figure 17).

B) Attach the 5” flexible pipe, using the collars

provided. Important: Make sure that the

plastic wrapping around the flexible pipe

will not be in contact with the fireplace.

C) Route the flexible pipe to the chosen location.

The ducting system can be installed either

in an upper room or in a lower room.

D) Attach the flexible pipe to the blower, using

the collars (Figure 18).

E) Fix the back draft damper to the blower

outlet.

& !TTACH A mEXIBLE PIPE TO THE FAN  mEXIBLE PIPE

adapter (square to round) and stretch it up

to the location where the heat is required.

G) At that point, the flexible pipe can be attached

to any air distribution grill.

H) Install the blower heating and cooling ther-

mostat (HCTW) in that part of the house to

be heated by the hot air duct. The thermostat

can be switched to a cooling thermostat and

installed in the same room as the unit. This

thermostat will turn on the blower when the

room where the fireplace is located becomes

too hot.

This option requires electricity. Make sure that

the connections to the blower have been made

according to the local codes and comply with

their requirements (see instruction provided

with the thermostat). For more information

regarding central forced and ducting, refer

to the BISFWK-1 installation sheet provided

with the kit.