3.14.2 I/F (Interface) Mode

The Interface (I/F) Mode is a bit-coded byte that you enter in hexadecimal notation.

Table 6 - Interface Mode Options

I/F Mode Option

7 6

5

4

3

2

1

0

RS-232C

(1)

0

0

RS-422/485

0

1

RS-485

2-wire

1

1

7

Bit

1

0

8

Bit

1

1

No

Parity

0

0

Even

Parity

1

1

Odd

Parity

0

1

1 Stop bit

0

1

2 Stop bit

(1)

1

1

(1) 2 stop bits are implemented by software. This might have influence on performance.

Note: RS-422/485 I/F Modes are supported on XPort-03 with firmware 6.1.0.0 and above.

The following table demonstrates how to build some common Interface Mode settings:

Table 7 - Common Interface Mode Settings

Common I/F Mode Setting

Binary

Hex

RS-232C, 8-bit, No Parity, 1 stop bit

0100 1100

4C

RS-232C, 7-bit, Even Parity, 1 stop bit

0111 1000

78

3.14.3 Flow

Flow control sets the local handshaking method for stopping serial input/output.

Table 8 - Flow Control Options

Flow Control Option

Hex

No flow control

00

XON/XOFF flow control

01

Hardware handshake with RTS/CTS lines (see note)

02

XON/XOFF pass characters to host

05