Lennox International Inc. 10ACB User Manual

Page 11

Advertising
background image

3DJH 

blocked or dirty coil. The low pressure switch (SPST,
NO) protects the system compressor from damage due
to loss of charge. The switch will trip at 15 +/-- 5 psig
(103 +/-- 34 kPa) and automatically resets at 25 +/--3 psig
(172 +/-- 21 kPa).

Refrigerant Sight Glass (Option Units ONLY)

A refrigerant sight glass is provided in the bag assem-
bly for field installation. The sight glass can be installed
in the liquid line to help monitor system charge.

0$,17(1$1&(

:$51,1*

(OHFWULF VKRFN KD]DUG &DQ FDXVH LQMX

U\ RU GHDWK %HIRUH DWWHPSWLQJ WR SHU

IRUP DQ\ VHUYLFH RU PDLQWHQDQFH WXUQ

WKH HOHFWULFDO SRZHU WR XQLW 2)) DW GLV

FRQQHFW VZLWFK HV  8QLW PD\ KDYH

PXOWLSOH SRZHU VXSSOLHV

At the beginning of each cooling season, the system
should be checked as follows:

1-- Clean and inspect condenser coil. Coil may be

flushed with a water hose. Make sure power is off
before cleaning.

2-- Visually inspect connecting lines and coils for evi-

dence of oil leaks.

3-- Check wiring for loose connections.
4-- Check for correct voltage at unit (unit operating).
5-- Check condenser fan motor amp--draw.

Unit nameplate _________ Actual ____________ .
127(   ,I RZQHU FRPSODLQV RI LQVXIILFLHQW FRROLQJ WKH
XQLW VKRXOG EH JDXJHG DQG UHIULJHUDQW FKDUJH
FKHFNHG 5HIHU WR VHFWLRQ RQ UHIULJHUDQW FKDUJLQJ LQ
WKLV LQVWUXFWLRQ

Evaporator Coil

1-- Clean coil, if necessary.
2-- Check connecting lines and coils for evidence of oil

leaks.

3-- Check condensate line and clean, if necessary.

Indoor Unit

1-- Clean or change filters.
2-- Adjust blower speed for cooling. The pressure drop

over the coil should be measured to determine the
correct blower CFM. Refer to the unit information
service manual for pressure drop tables and proce-
dure.

3-- Belt Drive Blowers -- Check belt for wear and proper

tension.

4-- Check all wiring for loose connections
5-- Check for correct voltage at unit (blower operat-

ing).

6-- Check amp-draw on blower motor

Unit nameplate_________ Actual ____________.