Warning, Setting the unit, Slab mounting – Lennox International Inc. 10ACB User Manual

Page 3: Roof mounting, Electrical, Line voltage, 24v, class ii circuit, 3djh, Figure 2, 10acb typical field wiring diagram

Advertising
background image

3DJH 

SETTING THE UNIT

Refer to unit dimensions on page 2 for sizing mounting
slab, platforms or supports. Refer to figure 1 for instal-
lation clearances.

INSTALLATION CLEARANCES

FIGURE 1

36

(914 mm)

*36

(914 mm)

36

(914 mm)

NOTE—48 inch clearance required on top of unit.

*NOTE—One side must be 36 inches. Two side may be 12”.

*36

(914 mm)

Slab Mounting

When installing unit at grade level, install on a level
slab high enough above grade to allow adequate drain-
age of water. Top of slab should be located so run--off
water from higher ground will not collect around unit.

Roof Mounting

Install unit at a minimum of 4 inches above the surface

of the roof. Care must be taken to ensure weight of unit

is properly distributed over roof joists and rafters. Ei-

ther redwood or steel supports are recommended.

ELECTRICAL

In the U.S.A., wiring must conform with current local
codes and the current National Electric Code (NEC). In
Canada, wiring must conform with current local codes
and the current Canadian Electrical Code (CEC). Refer to
the furnace or blower coil installation instructions for
additional wiring application diagrams and refer to
unit rating plate for minimum circuit ampacity and
maximum overcurrent protection size.

WARNING

Unit must be grounded in accordance with nation-

al and local codes. Electric Shock Hazard.

Can cause injury or death.

Line Voltage

To facilitate conduit, a hole is provided in bottom of the
control box. Connect conduit to hole in control box
with proper conduit fitting.
127( 8QLWV DUH DSSURYHG IRU XVH ZLWK FRSSHU FRQGXF
WRUV RQO\

24V, Class II Circuit

24V, Class II Circuit connections are made up in the low
voltage junction box. Refer to figure 2 for field wiring
diagram.
NOTE -- A complete unit wiring diagram is located in-
side the unit control box cover.

TO

COOLING

SPEED

TO

HEATING

SPEED

;

4+

9

/

40

CONDENSING UNIT

TYPICAL INDOOR UNIT

ROOM THERMOSTAT

POWER

GROUND

PER NATIONAL

AND LOCAL

CODES

24v

TRANSFORMER

24V

CLASS II

JUNCTION

BOX

TO

HEATING

CONTROLS

TO 24V CLASS II POWER SOURCE

-- 20 VA MINIMUM

K3 INDOOR BLOWER RELAY

NOTE--IF INDOOR UNIT IS NOT EQUIPPED WITH

BLOWER RELAY, IT MUST BE FIELD PROVIDED

AND INSTALLED (P--8--3251 OR EQUIVALENT)

NOTE--SEE UNIT WIRING DIAGRAM

FOR POWER SUPPLY CONNECTIONS.

24V CLASS II INSTALLED AT FACTORY

24V CLASS II FIELD INSTALLED

FIGURE 2

Y1

C

+

T1

R

W1

G

C

W2

10ACB TYPICAL FIELD WIRING DIAGRAM