***Each system is pre-charged with enough refrigerant to charge 25 ft. of line and the interior unit.

NOTE: Systems having the outdoor unit mounted above the indoor unit (e.g. basement
installations) have the following additional requirement:
For systems with elevation of 25 ft. (see figure A), refrigerant lines must be oil trapped
between 8 ft. and 12 ft. of elevation.
For systems with elevation of greater than 25 ft. Refrigerant lines must be oil trapped at
least every 12 ft. of elevation.

* Each system should have a 6-8 inch inverted trap at the condensing unit if mounted above

indoor unit.

17

Mini-Split

Standard

Single Zone

Type

A/C

A/C

A/C

A/C

A/C

H/P

H/P

H/P

H/P

H/P

System Model #

LS090CP

LS120CP

LS180CP

LS240CP

LS302CP

LS090HP

LS120HP

LS180HP

LS240HP

LS302HP

Indoor

36V DC

36V DC

36V DC

36V DC

36V DC

36V DC

36V DC

36V DC

36V DC

36V DC

BTUs

9,000

11,500

18,000

22,500

28,000

9,800

11,500

19,500

22,500

28,000

Rated

Amps

7.0

10.5

8.6/9.5

11.5/12.5

14.5/15.6

10.5

10.5

11.5/12.5

11.5/13.0

14.5/15.6

MCA*

15

15

15

20

25

15

15

20

20

25

MOP**

15

25

20

30

30

25

30

30

30

30

Electrical Specifications

Outdoor

115

115

230/208

230/208

230/208

115

115

230/208

230/208

230/208

Voltage

All equipment single phase.

NOTE: Recommend shielded cable for low voltage wiring.
Please see local electrical codes for proper wire specifications.

*Minimum Circuit Ampacity

**Maximum Overcurrent Protection

***For LS180HP, LS240CP/HP, LS302CP/HP

Wire Size

Minimum AWG

14-3

12-3***

Indoor/Outdoor Connecting Cable Shielded

18-4

Mini Split

Standard

Single Zone

Type

A/C

A/C

A/C

A/C

A/C

H/P

H/P

H/P

H/P

H/P

System
Model #

LS090CP

LS120CP

LS180CP

LS240CP

LS302CP

LS090HP

LS120HP

LS180HP

LS240HP

LS302HP

Pipe size

Liquid

Suction

1/4"

3/8"

1/4"

1/2 "

1/4"

1/2 "

1/4"

5/8"

1/4"

5/8"

1/4"

1/2"

1/4"

1/2 "

1/4"

5/8 "

1/4"

5/8"

1/4"

5/8"

BTUs

9,000

11,500

18,000

22,500

28,000

9,000

11,500

19,500

22,500

28,000

Additional
Refrigerant

0.25 oz./ft.

0.25 oz./ft.

0.25 oz./ft.

0.25 oz./ft.

0.35 oz./ft.

0.25 oz./ft.

0.25 oz./ft.

0.25 oz./ft.

0.25 oz./ft.

0.35 oz./ft.

Max. length
each pipe

50'

50'

100'

100'

100'

50'

50'

100'

100'

100'

Max.
elevation

25'

25'

50'

50'

50'

25'

25'

50'

50'

50'

Refrigerant Line & Formula Specifications***

25' maximum

8' minimum
12' maximum

OIL TRAP

INDOOR UNIT

OUTDOOR UNIT

MINI-SPLIT STANDARD SINGLE ZONE

ELECTRICAL & REFRIGERATION

QUICK REFERENCE

Figure A.
Example: 25 ft. maximum elevation.
Must install trap inverted.