Electrical specifications, Refrigerant line & formula specifications – LG LA090HP User Manual

Page 25

Advertising
background image

22

Zone

Flex Multi Split

Indoor Units

Outdoor Units

Model

LMI090CP

LMA090CP

LMI120CP

LMA120CP

LMA121CPM

LMI090HP

LMA090HP

LMI120HP

LMA120HP

LMA121HPM

LMO240C

LMO360C

LMO240H

LMO360H

Indoor

36V DC

36V DC

36V DC

36V DC

36V DC

36V DC

36V DC

36V DC

36V DC

36V DC

BTUs

9,000

9,000

12,000

12,000

12,000

9,000

9,000

12,000

12,000

12,000

24,000

36,000

24,000

36,000

Electrical Specifications

Outdoor

230/208

230/208

230/208

230/208

Voltage

*Minimum Circuit Ampacity

**Maximum Overcurrent Protection

Wire Size

Minimum AWG

14-3

Indoor/Outdoor Connecting Cable Shielded

18-4

Flex Multi Split

Type

A/C

A/C

A/C

A/C

A/C

H/P

H/P

H/P

H/P

H/P

Model

LMI090CP

LMA090CP

LMI120CP

LMA120CP

LMA121CPM

LMI090HP

LMA090HP

LMI120HP

LMA120HP

LMA121HPM

Pipe size

Liquid

Suction

1/4"

1/4"

1/4"

1/4"

1/4"

1/4"

1/4"

1/4"

1/4"

1/4"

BTUs

9,000

9,000

12,000

12,000

12,000

9,000

9,000

12,000

12,000

12,000

Additional
Refrigerant

0.21 oz./ft.

0.21 oz./ft.

0.21 oz./ft.

0.21 oz./ft.

0.21 oz./ft.

0.21 oz./ft.

0.21 oz./ft.

0.21 oz./ft.

0.21 oz./ft.

0.21 oz./ft.

Max. length
each pipe

50'

50'

50'

50'

50'

50'

50'

50'

50'

50'

Max.
elevation

25'

25'

25'

25'

25'

25'

25'

25'

25'

25'

Refrigerant Line & Formula Specifications***

25' maximum

8' minimum
12' maximum

OIL TRAP

INDOOR UNIT

OUTDOOR UNIT

3/8"

3/8"

3/8"

3/8"

3/8"

3/8 "

3/8"

3/8"

3/8"

3/8"

HIGH WALL DUCT LESS

FLEX MULTI SPLIT • DUAL & TRI ZONE

ELECTRICAL & REFRIGERATION

QUICK REFERENCE

NOTE: Recommend shielded cable for low voltage wiring.
Please see local electrical codes for proper wire specifications.

All equipment single phase.

Type

A/C

A/C

A/C

A/C

A/C

H/P

H/P

H/P

H/P

H/P

A/C

A/C

H/P

H/P

Rated

Amps

0.5

1.3

0.5

1.3

0.5

0.5

1.3

0.5

1.3

0.5

11.1

16.6

11.1

16.6

MCA*

20

20

20

20

MOP**

20

30

20

30

***Dual Zone: exterior unit has sufficient refrigerant for charging two indoor coils and a 25 ft. line set per indoor unit.

Tri Zone: exterior unit has sufficient refrigerant for charging three indoor coils and a 25 ft. line set per indoor unit.

NOTE: Systems having the outdoor unit mounted above the indoor unit (e.g. basement installations) have the

following additional requirement:
For systems with maximum elevation of 25 ft. (see Figure A), refrigerant lines must be oil
trapped between 8 ft. and 12 ft. of elevation.
For systems with elevation of greater than 25 ft. Refrigerant lines must be oil trapped at least every 12 ft.
of elevation.

* Each system should have a 6-8 inch inverted trap at the condensing unit if mounted above indoor unit.

Figure A.
Example: 25 ft. maximum elevation.