Caution, Transfer voltage selectors (dip switches) – Liebert PSP User Manual

Page 17

Advertising
background image

13

Transfer Voltage Selectors (DIP Switches)

The two-position DIP switch control on the rear panel, as shown

below, allows the operator to select the utility transfer voltage at

which the UPS will switch to battery power.

The factory default settings are 185VAC - 270VAC. DIP switch posi-

tions for each voltage setting are as follows:

DIP switch settings

Left

Right

Setting

↑ Up

↑ Up

185 - 270VAC (default)

↑ Up

↓ Down

185 - 280VAC

↓ Down

↑ Up

175 - 270VAC

↓ Down

↓ Down

175 - 280VAC

!

CAUTION

Never change the voltage settings while the UPS is ON and

powering connected loads. Change DIP switches only when

the UPS is OFF.

!

CAUTION

To ensure protection of the connected equipment, the DIP

switch settings should match the nominal utility input

voltage. DIP switch settings not matching the nominal

utility could potentially damage connected equipment.

185-270V

185-280V

175-270V

175-280V

Refer to user's manual
for voltage setting

Rear of UPS

DIP Switches