Guide to status indicators – Liebert PSP User Manual

Page 24

Advertising
background image

20

T

ROUBLESHOOTING

The information below indicates various symptoms a user may

encounter in the event the PowerSure PSP experiences a problem. Use

this information to determine whether external factors caused the

problem. See Troubleshooting Chart for suggested remedy.

Guide to Status Indicators

1. The Fault indicator illuminates, indicating the

UPS detected a problem.

2. An alarm sounds, alerting that the UPS

requires attention. The alarm can be silenced

except for low battery, overload and

over-temperature warning conditions.

3. Utility and/or Battery indicators may be

illuminated as a diagnostic aid to the operator,

as shown below:

Fault

Indicator

Utility

Indicator

Battery

Indicator

Diagnosis/

Audible Alarm

Green
ON

Normal operation with utility
power present; no beep.

Green
ON

UPS is operating on battery;
beep every 10 seconds.

Green
ON

Battery test has been
initiated; no beep.

Green
ON

Amber
Flashing

Battery needs to be replaced;
long beep every minute.

Amber
Flashing

Low battery warning; beep
every half-second.

Green
Flashing

Green
ON

Overload warning, load is
>100%; beep every half-
second.

Green
Flashing

Overload shutdown, load
exceeds UPS capacity
(110%); continuous beep.

Green
ON

Green
ON

Over temperature (overtemp)
warning; beep every
5 seconds (Normal mode).

Green
ON

Green
ON

Over temperature (overtemp)
warning; beep every
5 seconds (Battery mode).

Green
ON

Over temperature (overtemp)
shutdown; long beep every
5 seconds.

Red
Flashing

Green
ON

UPS is on, fault warning;
continuous beep.

Red
ON

UPS has failed & shut down;
continuous beep.

Fault
Indicator

Utility
Indicator

Battery
Indicator