Battery run times – Liebert PSP User Manual
Page 27
Advertising
23
Battery Run Times
AGENCY
Safety
EN 50091-1; CE low voltage directive; TUV Certificate
Surge
EN61000-4-5, Level 3, Criteria A
ESD
EN61000-4-2, Level 3, Criteria A
Susceptibility
EN61000-4-3, Level 3, Criteria A
Electrical Fast
Transient/Burst
EN61000-4-4, Level 4, Criteria A
Emissions
EN 50091-2, Class B; CE EMC directive
Conducted Immunity
EN61000-4-6, Level 3, Criteria A
Harmonics
EN61000-3-2
Flicker
EN61000-3-3
Transportation
ISTA Procedure 1A
Load %
500VA
650VA
5
156
192
10
113
95
20
49
42
30
31
30
40
22
21
50
17
14
60
11
13
70
9
10
80
7
7
90
5
6
100
4
5
NOTE
Approximate discharge times are in minutes and at 25°C
(77°F) with a resistive load.
Advertising