Panasonic 6367 User Manual

Fire alarm systems duct detector chamber 6367

Advertising
background image



Panasonic Electric Works Fire & Security Technology Europe AB

Citadellsvägen 23, SE-211 18 Malmö, Sweden

Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99

[email protected] • www.panasonic-fire-security.com

Fire alarm systems

Duct detector

chamber

6367

• Only one pipe is required
• Simple installation
• For conventional as well as analog and addressable systems

General

The Uniguard Duct detector chamber 6367
is used when smoke is to be detected in a
ventilation duct. Both the "venturi pipe" and
the housing, where a smoke detector is to be
placed, are especially designed for optimum
airflow through the detector. The housing is
made of grey ABS and the venturi pipe is
made of aluminium. Supplied with two
compression glands for cable entry.

6367 can be used in conventional as well as
analog fire alarm systems, depending on the
detector placed inside the housing.

The Photoelectric smoke detector 4352,
plugged in the base 2324, is used in a
conventional system (zone line input). An
attached space ring (11 mm) is required
between the base and the housing.

The Analog photoelectric smoke detector
4301, plugged in the analog base 3312, is
used in an analog and addressable system.
An attached space ring (19 mm) is required
between the base and the housing.

Venturi pipe 6371

The venturi pipe is available in three lengths
and can easily be shortened to suit the
ventilation duct. An attached plug is to be
placed in the end of the pipe.

A ventilation duct with a width < 0.6 m
(diameter) requires a 0.6 m venturi pipe
(6371-06), ended inside the duct.

A ventilation duct with a width > 0.6 m
(diameter) requires an 1.5 or 2.8 m venturi
pipe (6371-15 / -28), ended outside the duct.

See figure on the opposite page.

Air flow indicator

A built-in air flow indicator gives a
confirmation that the air from the ventilation
duct is flowing through the venturi pipe and
the detector. If not, a booster fan 6373 is
available as an option.

Accessories

Bracket 6372, to be used when 6367 shall be
mounted on a round ventilation duct. See
figure on the opposite page.

Booster fan 6373, to be used when the air
flow indicator is indicating no or very small
air flow. The fan shall be mounted inside
the housing and connected to the terminal
block. External power supply (24 V AC, 50
mA) is required.

Filter 6374, can be used in an extremely
dirty environment, as in a saw mill, a timber
yard, etc. The filter shall be placed inside
the housing, in a slot just before the detector.

Product applications

The Duct detector chamber can be used in
the systems EBL500 / 512 / 128 / 1000 /
2000. It is intended for indoor use and in
dry premises.

Advertising