Panasonic 6367 User Manual

Page 2

Advertising
background image

All technical features and data are subject to changes without notice, resulting from continuous development and improvement.

Product Leaflet

Date of issue

Revision / Date of revision

MEW00435 2004-02-05

2

/

2006-08-31

Type numbers

6367

Duct detector chamber (NOTE! Detector & base have to be ordered
separately).

6371-06

Venturi pipe 0.6 m (Incl. end plug.)

6371-15

Venturi pipe 1.5 m (Incl. end plug, plastic gasket and membrane gland TET
26-35.)

6371-28

Venturi pipe 2.8 m (Incl. end plug, plastic gasket and membrane gland TET
26-35.)

6372 Bracket

6373

Booster fan (ext. 24 V AC, 50 mA required)

6374 Filter

Left: How to suit the pipe to different widths of the ventilation duct. Right: The Bracket 6372.

Attached with each Duct detector chamber are detailed mounting and installation instructions.

Technical data

Duct air flow velocity (m/s)

0.2 to 15

Ambient temperature (

°C)

operating

storage

-10 to +50
-25 to +75

Ambient humidity (% RH)

max. 95, non condensing

Ingress Protection rating

IP54

Size L x W x H (mm)

287 x 150 x 110 (the housing only)

Weight (g)

680 (the housing only)

Construction / Colour

ABS / Grey (RAL7035)

Compression glands

M16x1.5 for cable Ø=3-10 mm

Approvals

CE; EN 54

See also Product Leaflets / Technical data for the base and the detector to be used.

6367 can be mounted vertical or
horizontal on the duct and
3 x the duct diameter before or
5 x the duct diameter after a
disturbance (i.e. a bend, a filter or
a damper.