4300 analog multi detector – Panasonic 4300 User Manual

Page 2

Advertising
background image

All technical features and data are subject to changes without notice, resulting from continuous development and improvement.

Product Leaflet

Date of issue

Revision / Date of revision

MEW00307 2003-04-24

6

/

2008-09-15

Type number

4300

Analog multi detector

+

COM loop

Ext. LED

SA (L)

SA (L)

C.i

.e

. EBL5

12

/ EBL

128

C

O

M

lo

op

in

p

u

t

SB (C)

SB (C)

SB

SB

E-

E-

SA

SA

E+

E+

Mark

Mark

SB

E-

SAo

E+

Mark

SAi

3312

4313

3312FL/F

In the detector:

See also "Engineering Instructions for detectors Type 430x".

SA/SB Contact pins for COM loop / address setting tool 3314
E+/E- Contact pins for External LED
Tl

Type number label; Detector type

Al

Address label; For the programmed COM loop address to be written.

Lsh

Locking screw hole (prepared for drilling through detector body)

Ls Locking

screw

Prepared for mechanical locking with analog base 3312x / 4313. One hexagon socket screw
(Ls) is attached (1.5 mm Hex key to be used). The 2.5-2.7 mm hole (Lsh) has to be drilled.

Technical data

Voltage (V DC)

rated
allowed
normal (on COM loop)

28
12-30
24

Current consumption at nom. volt.
from COM loop (mA)

quiescent
active (incl. internal LED)
ext. LED (connected via base 3312)


0.3
2.3
max. 2

Ambient temperature (

°C)

operating
storage

-10 to +50
-25 to +75

Ambient humidity (% RH)

max. 95, non condensing

Ingress Protection rating (estimated)

IP 51

Sensitivity (obscuration; %/m)


NORMAL mode
2330 mode

Depending on mode.


3.6 / 3.0 / 2.4 (Low / Normal / High)
5
>2.5 in combination with temp. rate-of-rise (depending on algorithm)

Sensitivity (T=

°C; deltaT=

°

C/min.)


NORMAL mode
2330 mode

Depending on mode.


56 / 46 / 60 / 74 (A1; < 4 / A1; > 4 / A2 (S) / B (S))
57; 6.43
57; >1.07 in combination with smoke obscur. (depending on algorithm)

Size

∅ x h (mm)

102 x 44

Weight (g)

70

Construction / Colour

Modified polycarbonate / Grey (N8, Munsell colour code)

Approvals

05 EC Certificate no. 0786-CPD-20145; EN54-7 (smoke)
05 EC Certificate no. 0786-CPD-20146; EN54-5 Class P (heat)

SB

SA

E-

E+

Tl

Ls

Lsh

Al

The detector is plugged in the analog base 3312x / 4313.
The COM loop / Ext. LED are connected to the analog base.

Advertising