PVI Industries 27 N 125A-MXS User Manual

Maxim • packaged gas water heater

Advertising
background image

Product is patented in the U.S., Canada, and Mexico.

PVI INDUSTRIES, LLC

FORT WORTH, TEXAS 76111

PV 6139 08/07

(800) 784-8326

• www.pvi.com

MAXIM • PACKAGED GAS WATER HEATER

NICKELSHIELD

®

NICKEL-PLATED STORAGE TANK

125 GALLON TANK SERIES

MODEL NUMBER

20 N 125A-MXS

27 N 125A-MXS

40 N 125A-MXS

54 N 125A-MXG 72 N 125A-MXG

80 N 125A-MXG

GPH Recovery at 40° to 120° F

245

330

490

670

900

1000

GPH Recovery at 40° to 140° F

195

260

390

540

720

800

Input

Btu/h

199,000 270,000 399,000 540,000 720,000 800,000

*

Min. inlet flow gas pressure " W.C.

5.5

5.5

5.5

4.5

4.5

4.5

*

Max static gas pressure “W.C.

9

9

9

14

14

14

A Cold Inlet - NPT

2

2

2

2

2

2

B Hot Outlet - NPT

2

2

2

2

2

2

C

Drain

-

NPT

1 1 1 1 1 1

D I - Beam Skids

3 x 34-1/2

3 x 34-1/2

3 x 34-1/2

3 x 34-1/2

3 x 34-1/2

3 x 34-1/2

E

Overall

Depth

45 45 45 53 52 54

F

Overall

Height

75 75 75 82 82 82

G Flue Outlet Diameter

5

6

7

8

10

10

H Gas Inlet - NPT

1/2

3/4

3/4

1

1-1/4

1-1/4

J Motor HP 120 V, 1Ø, 60 Hz.

1/6

1/6

1/6

1/3

1/3

1/3

K Motor

Amps

1.75

1.75

1.75

8

8

8

L

Height

to

Outlet

65 65 65 73 73 73

M

Height

to

Inlet

28 28 28 36 36 36

Approx. Shipping Weight - lbs

1020

1070

1130

1260

1370

1390

ASHRAE 90.1 compliant.
Models with suffix “MXS” are registered as low NOx water heaters in California and Texas
* The information presented is for natural gas 0.6 S.G. – For operation with propane (LP gas), consult the factory.
* For gas pressures outside of this range, consult factory.
Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see form # PV 6137.


STANDARD ELECTRICAL CONNECTIONS

VENTING REQUIREMENTS

CONTROL VOLTAGE: 120V, 1Ø, 60 Hz, 2 amps

SEE ABOVE CHART FOR BLOWER MOTOR AMPS

-.02" TO -.06" W.C. (negative pressure)

TYPE B VENTING

THE ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED

UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY.

FOR PROPER VENT SIZING, CONSULT THE NATIONAL FUEL

GAS CODE UNDER “FAN-ASSISTED”



PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND
SPECIFICATION WITHOUT NOTICE.

1. Control Enclosure
2. ASME Temperature &
Pressure Relief Valve
3. 3” NPT Handhole

Advertising
This manual is related to the following products: