Installing the external bestlink adapter – Powerware BestLink IPK-0319 User Manual

Page 10

Advertising
background image

Installation

4

BestLink SNMP/WEB Adapter User’s Guide

:

LTM-1343 B Draft 10/03/2001

Set both DIP switches
to the

0 (off) position

1
0

Slide the adapter into
the UPS BestDock

Figure 2. Installing the Internal BestLink Adapter

4. Set both DIP switches on the adapter to the

0

(off) position.

5. Connect an active 10BaseT cable to the network connector on the

BestLink Adapter.

NOTE For an internal BestLink Adapter in a FERRUPS 0800, Axxium Pro, or Powerware 9170
UPS, you MUST change the Config BestDock parameter for that UPS to BestDock 1 or 2 as
applicable. Refer to the UPS user’s guide for detailed instructions on how to change the
parameter through the UPS front panel configuration menu.

6. Continue to “Configuration” on page 6.

Installing the External BestLink Adapter

To install the external BestLink SNMP/WEB Adapter, perform the following
steps:

1. Verify that the UPS is turned off.

2. Use the supplied serial cable labeled “UPS” to connect the UPS port

on the BestLink Adapter to the UPS communication port.

If connecting to a FERRUPS model with a DB-25S communication
port, you must also use the supplied DB-9 to DB-25 adapter labeled
INT-0013B.

3. Set both DIP switches on the adapter to the

0

(off) position.