Powerware BestLink IPK-0319 User Manual

Page 26

Advertising
background image

UPS Power Management

20

BestLink SNMP/WEB Adapter User’s Guide

:

LTM-1343 B Draft 10/03/2001

Turning the UPS On and Off

The BestLink SNMP/WEB Adapter supports the ability to remotely turn off
the UPS and its supported load. It also supports the ability to reboot the UPS
(cycling output power off and then back on), as well as the ability to schedule
shutdowns and restarts on a predetermined basis.

Selecting

Control

from the menu at the top of the home page provides a page

that allows the Superuser to turn the UPS off. In addition, you may initiate a
battery test and enable or disable any scheduled shutdowns or startups as
specified in the UPS shutdown schedule table (accessed from the
Configuration menu).

Forcing the UPS to Shut Down

1. Select

Configuration

from the menu at the top of the home page, then

UPS Shutdown and Restart Settings

.

2. Verify that

UPS to Shut Down following Client OS Shutdown

is set to

YES

.

3. Log in as a Superuser.

4. Set the appropriate

Delay Before Shutdown

in minutes to ensure that

any NetWatch clients and their respective operating systems have
enough time to complete their shutdown. The default is three
minutes, but you may wish to increase or decrease this value as
appropriate for your system.

5. If you want to shut off the UPS and have it stay off (requiring local

interaction to turn it back on), change

Restart UPS once AC Power

Returns

to

NO

.

If you want to effectively reboot the UPS and the associated load,
then set

Restart UPS once AC Power Returns

to

YES

. The UPS will

automatically restart when utility power returns after a brief delay.

6. After choosing the desired values, select

Set Values

to update the

BestLink Adapter with the new information.

7. You may then select

Control

from the menu at the top of the home

page and select

Turn UPS Off

.

8. To initiate the shutdown sequence, select

Set Values

which instructs

the BestLink Adapter to send the appropriate information to the UPS
and any clients running the NetWatch shutdown client software.