Pentair Water Commercial Pool and Spa

Therefore, the temperature difference between
the inlet and out pipes will be so small as to be
difficult to sense by touching the two pipes.

2I. Boiler By-Pass Piping

All Model MT pool boilers are equipped with an

automatic flow control valve. Do not install a manual
bypass valve unless the normal filtration rate exceeds
300 GPM. If the normal filtration rate exceeds that
figure:

1.

Install the manual bypass valve as illustrated in
Figure 7.

2.

Install a thermometer in the threaded opening in
the rear header as shown in Figure 8.

3.

Set the manual bypass valve as follows:

a.

Clean or backwash the filter completely.

b.

Close the manual bypass valve completely.

c.

Close the boiler’s main gas valve.

d.

Start the filtration system with all valves set
for normal filtration.

e.

After 3 minutes, record the thermometer
reading (this is the pool water temperature).

f.

Open main gas valve and turn the
thermostat to its highest setting to start the
boiler.

g.

Gradually open the bypass valve until the
temperature difference shown in column 6
of Table 4 is achieved. For example, if the
temperature reading in Step “e” was 60
degrees, and the boiler is a Model 3500, the
thermometer should read 75 degrees. Make
sure this temperature difference remains
constant for at least 5 minutes.

h.

Remove the handle from the bypass valve
to prevent anyone from changing the
setting. The automatic flow control valve
will maintain proper flow through the
boiler regardless of the reduced water flow
due to a dirty or clogged filter.

2J. Automatic Chlorinators

A concentration of chlorine in the boiler can be

very destructive. Therefore, the following rules
regarding the installation and operation of automatic
chlorinators must be followed.

1.

The chlorinator should be installed so that it
introduces the gas or solution downstream from
the boiler.

2.

The chlorinator should be wired so that it cannot
operate unless the filter pumps running.

3.

The chlorinator should be provided with an anti-
syphoning device so that when the pump shuts
off, chlorine will not syphon back into the boiler.

4.

When the chlorinator is installed in the system
where the chlorine flows through the boiler,
corrosion can occur. Excessive concentrations of
chlorine, caused by improper adjustment or
failure of the chlorination equipment, can cause
boiler damage which is not covered by the
warranty.

2K. Pressure Switch

The pressure switch on the boiler is factory set at

4 psi. Do not tamper with the switch unless the boiler
is installed more than 3 feet below the surface of the

Figure 7. Manual By-Pass Installation.

Figure 8. Thermometer Location.

Bypass

Min.

Max. Temp.

Spring

Flow

Bypass

Rise

Indoor Outdoor Part

Color

Req'd

Valve

at Rear

Size

Size

No.

Code (GPM)Cap. (GPM) Header

2000

------

S220

Black

110

300

15

2450

2200

S221

White

134

300

15

3050

2800

S221

White

167

300

15

3500

3200

S222 Brown

191

300

15

4050

3600

S222 Brown

221

300

15

4500

4000

S222 Brown

246

300

15

5000

4500

S222 Brown

273

300

15

Table 4. By-Pass Valve Adjustments.