Automatic operation, Dry operation 9.7.3. heating operation, Operation mode selection – Panasonic CU-TE12DKE User Manual

Page 30: Setting temperature shift in automatic operation

Advertising
background image

Airflow direction, Fan speed and Setting temperature are
optimized.

“Intake Air temperature - Remote controller setting
temperature” is detected every 20 seconds by indication
from indoor unit and controlled to each area.

Quick Dry

Unit forcibly turns to Quick Dry operation for 5

minutes after POWERFUL ON even through it is in the stable
area. If unit gets out of the area, it turns to Chilly Dry operation.
Chilly Dry

Discharge Air temperature is kept low by

changing fan speed according to room temperature and chilly
feeling is produced.

Airflow direction, Fan speed and Setting temperature are
optimized.

“Intake Air temperature - Remote controller setting
temperature” is detected every 20 seconds by indication
from indoor unit and controlled to each area.

Quick Heating

Unit forcibly turns to Quick Heating operation

for 5 minutes after POWERFUL ON even through it is in the
stable area. If unit gets out of the area, it turns to Warm Heating
operation.
Warm Heating

Discharge Air temperature is kept high by

changing fan speed according to room temperature and warm
feeling is produced.

9.7.2. Dry Operation

9.7.3. Heating Operation

9.8. Automatic Operation

Operation mode (Cooling, Dry and Heating) is automatically selected.

Operation mode is selected at the beginning of unit operation and every 30 minutes. Temperature, Fan speed and Airflow
directions are set with remote controller.

9.8.1. Operation Mode Selection

Operation mode is selected according to outdoor temperature, intake air temperature and setting temperature.
1. "Heating" is selected when intake air temperature is below 16 °C.
2. "Cooling" is selected when intake air temperature is 25 °C or more. (But, when intake air temperature is 16 °C or more.)
3. Selectable range of "Heating" and "Cooling" for setting temperature on the remote controller is increased when outside air

temperature is below 25 °C.

9.8.2. Setting Temperature Shift in Automatic Operation

When Cooling mode is selected, setting temperature is shifted to +1 °C.

When Heating mode is selected, setting temperature is shifted to -1 °C.

30

CS-TE9DKE CU-TE9DKE / CS-TE12DKE CU-TE12DKE