Error code table – Panasonic CU-TE12DKE User Manual

Page 65

Advertising
background image

13.3.2. Error Code Table

Diagnosis

display

Abnormality / Protection control

Abnormality

Judgement

Emergency

operation

Primary location to verify

H11

Indoor / outdoor abnormal
communication

> 1 min after starting
operation

Indoor fan operation

only

Internal / external cable connections

Indoor / Outdoor PCB

H14

Indoor intake air temperature sensor
abnormality

Intake air temperature sensor
(defective or disconnected)

H15

Outdoor compressor temperature sensor
abnormality

Continue for 5 sec.

Compressor temperature sensor
(defective or disconnected)

H16

Outdoor Current Transformer open
circuit

Outdoor PCB

IPM (Power transistor) module

H19

Indoor fan motor mechanism lock

Indoor PCB

Fan motor

H23

Indoor heat exchanger temperature
sensor abnormality

Continue for 5 sec.

O

(Cooling only)

Heat exchanger temperature sensor
(defective or disconnected)

H26

Ionizer abnormality

Indoor PCB

Ionizer

H27

Outdoor air temperature sensor
abnormality

Continue for 5 sec.

O

Outdoor temperature sensor
(defective or disconnected)

H28

Outdoor heat exchanger temperature
sensor abnormality

Continue for 5 sec.

O

Outdoor heat exchanger
temperature sensor (defective or
disconnected)

H33

Indoor/Outdoor wrong connection

Indoor/Outdoor supply voltage

H97

Outdoor Fan Motor lock abnormality

Outdoor PCB

Outdoor Fan Motor

H98

Indoor high pressure protection

Air filter dirty

Air circulation short circuit

H99

Indoor heat exchanger anti-freezing
protection

Insufficient refrigerant

Air filter dirty

F11

Cooling / Heating cycle changeover
abnormality

4 times occurrence
within 30 minutes

4-way valve

V-coil

F91

Refrigeration cycle abnormality

2 times occurrence
within 20 minutes

No refrigerant

(3-way valve is closed)

F93

Outdoor compressor abnormal revolution

4 times occurrence
within 20 minutes

Outdoor compressor

F95

Cool high pressure protection

4 times occurrence
within 20 minutes

Outdoor refrigerant circuit

F96

IPM (power transistor) overheating
protection

Excess refrigerant

Improper heat radiation

IPM (Power transistor)

F97

Outdoor compressor overheating
protection

4 times occurrence
within 10 minutes

Insufficient refrigerant

Compressor

F98

Total running current protection

3 times occurrence
within 20 minutes

Excess refrigerant

Improper heat radiation

F99

Outdoor Direct Current (DC) peak
detection

7 times occurrence
continuously

Outdoor PCB

IPM (Power transistor)

Compressor

Note:

“O” - Frequency measured and fan speed fixed.

The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard
following by pressing the “RESET” button at remote controller.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error
Codes Table) by using remote controller or Auto Switch at indoor unit. However, the remote controller signal receiving sound is
changed from one “beep” to four “beep” sounds.