All technical features and data are subject to changes without notice, resulting from continuous development and improvement.

Product Leaflet

Date of issue

Revision / Date of revision

MEW01047 2008-01-23

2

/

2008-09-18

Type numbers

4375

Heat detector, 60

°C, class A2 S.

4376

Heat detector, 80

°C, class B S.

In the detector:

See also "Engineering Instructions for detectors Type 435x".

A

Contact for base 2324

B

Contact for base 2324

The detector is plugged in a base 2324. End-of-line device depending on the zone line input.

Technical data

Voltage (V DC)

rated
allowed
normal


24
10-30
24 (zone line voltage)

Current consumption at nom. voltage,
quiescent (mA)


Max. 0.015

Current limitation required, when
active (mA)

(EBL equipment has current limitation.)


Must be min. 6 and max. 100

Ambient temperature (

°C)


operating (Min. / Typical / Max.)

storage

4375 (A2 S):

4376 (B S):

-10 /+25 /+40

-10 /+40 /+60

-25 to +70

-25 to +70

Static response temperature (

°C)

55 (4375) and 72 (4376)

Ingress Protection rating (estimated)

IP51

Size

∅ x h (mm)

102 x 39

Weight (g)

54

Construction / Colour

Modified Polycarbonate / Grey (N8, Munsell colour code)

Approvals

07 EC Certificate no. 0786-CPD-20334 (4375); EN54-5 + A1
07 EC Certificate no. 0786-CPD-20335 (4376); EN54-5 + A1

A

B

The zone line is connected to the base 2324 (A+ & B-)
Ext. LED is connected to the base 2324 (A+ & L).