NI-DNET User Manual

Port Characteristics

Bus power .............................................. 0 to 30 V, 40 mA typical,

100 mA maximum

CAN-H, CAN-L..................................... –8 to +18 V, DC or peak, CATI

Safety

The NI-CAN hardware meets the requirements of the following standards
for safety and electrical equipment for measurement, control, and
laboratory use:

EN 61010-1, IEC 61010-1

UL 3111-1, UL 61010B-1

CAN/CSA C22.2 No. 1010.1

Note

For UL and other safety certifications, refer to the product label, or visit

ni.com/hardref.nsf

, search by model number or product line, and click the

appropriate link in the Certification column.

Pollution Degree .................................... 2

Maximum altitude .................................. 2,000 m

Indoor use only.

Electromagnetic Compatibility

Electrical emissions................................ EN 55011 Class A at 10 m FCC

Part 15A above 1 GHz

Electrical immunity................................ Evaluated to EN 61326:1997

+A2:2001, Table 1

CE, C-Tick, and FCC Part 15 (Class A) Compliant

Note

For EMC compliance, operate this device with shielded cabling.