National Instruments FP-RTD-122 User Manual

Features

Advertising
background image

323348B-01

April 2003

© 2002–2003 National Instruments Corp. All rights reserved.

FieldPoint™, National Instruments™, NI™, and ni.com™ are trademarks of National Instruments Corporation.
Product and company names mentioned herein are trademarks or trade names of their respective companies.
For patents covering National Instruments products, refer to the appropriate location: Help»Patents in your software,
the patents.txt file on your CD, or ni.com/patents.

FieldPoint Operating Instructions

FP-RTD-122 and
cFP-RTD-122

Eight-Channel Three-Wire RTD and
Resistance Input Modules

These operating instructions describe how to install and use the
National Instruments FP-RTD-122 and cFP-RTD-122 three-wire
RTD and resistance input modules (referred to inclusively as the
[c]FP-RTD-122). For details on configuring and accessing the
[c]FP-RTD-122 over a network, refer to the user manual for the
FieldPoint network module you are using.

Features

The [c]FP-RTD-122 is a FieldPoint RTD and resistance input
module with the following features:

Inputs for 100 and 1,000

Ω platinum RTDs (resistance

temperature detectors)

Built-in linearization for six TCR (temperature coefficient of
resistance, or alpha) values of RTDs

Direct resistance measurements in 400 and 4,000

Ω ranges

True three-wire compensation

16-bit resolution

Filtering against 50 and 60 Hz noise

Hot swappable

2,300 V

rms

transient overvoltage protection

–40 to 70 °C operation