Model 300dcs, Options, Engineering data – Lifebreath 95MAX User Manual

Page 10: Performance, Dimensions 300dcs

Advertising
background image

10

49 "

(1245)

STALE AIR

TO OUTSIDE

FRESH AIR

TO INSIDE

14 3/4"

(375)

19"

(483)

Ports

7" (178 mm)

CONDENSATE

DRAINS

BLOWERS

*NOTE:
Front clearance
of 25 inches (635 mm)
is recommended
for servicing unit.

MOTOR

FRESH AIR

FROM OUTSIDE

STALE AIR

FROM INSIDE

FILTER

DEFROST

DAMPER

DEFROST AIR

FROM INSIDE

FILTER

Ports

6" (150 mm)

METAL CLASPS

OPTIONS

99-104

Digital Electronic Timer - 20/40/60 min.

99-105

Programmable Ventilation Control (PVC) includes
Programmable Time Clock, Dehumidistat and Air
Sentry™

99-109

Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad.

99-250

Ventilation Dehumidistat - Dehumidistat designed to
accept remotely mounted Control Pad.

99-160

Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 7”
(178 mm)

99-161

Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 7”
(178 mm)

99-186

Weatherhoods, Two - 6” (150mm) c/w 1/4” (6mm)
mesh screen

WARRANTY

Units carry a LIFETIME warranty on the heat recov-

ery core and a 5 year replacement parts warranty.

TI-102-NE

1203

ENGINEERING DATA

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE

The cross-flow heat recovery core transfers heat between the
twoairstreams. The two cores are arranged for highly efficient counter
current airflow.

MOTORS AND BLOWERS - Each air stream has one centrifugal blower
driven by a common PSC motor. 5 speed fan operation. 120 VAC, 2.9
Amps.

FILTERS - Washable air filters in exhaust and supply air streams.

MOUNTING THE HRV - Four threaded inserts at corners of case
designed to accept four reinforced polyester straps that are supplied with
the unit.

DEFROST - Damper defrost system.

DEHUMIDISTAT - Adjustable Internal Dehumidistat.

CASE - Twenty gauge prepainted galvanized steel (G60) for superior
corrosion resistance. Insulated to prevent exterior condensation.

Drain connections 2 - 1/2" (12 mm) OD.

CONTROLS - ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode,
Recirculation mode, (each mode has 5 speeds). Control pad can be
removed from HRV and remotely mounted.

WEIGHT 106 lbs. (48 kg)

SHIPPING WEIGHT 108 lbs. (49 kg )

PERFORMANCE

HVI CERTIFIED

Net supply airflow in cfm (L/s) against external static pressure

E.S.P

cfm

L/s

@ 0.1” (25 Pa)

265

(125)

@ 0.2” (50 Pa)

260

(123)

@ 0.3” (75 Pa)

250

(118)

@ 0.4” (100 Pa)

235

(111)

@ 0.5” (125 Pa)

220

(104)

Maximum Temperature Recovery

90%

Sensible Effectiveness
@ 117 cfm (55 L/s)

(CSA C439M)

90%

Sensible Efficiency
@ 117 cfm (55 L/s) 32°F (0

O

C)

79%

Sensible Efficiency
@ 117 cfm (55 L/s) -13°F (-25

O

C)

75%

VAC @ 60HZ

120

WATTS / Low speed

150

WATTS / High speed

333

Amp rating

2.9

300DCS FANCURVE

300

275

250

225

200

175

150

125

100

75

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

Air Flo

w

(cfm)

Static Pressure (inH

2

0)

HIGH SPEED

*

MEDIUM HIGH SPEED

MEDIUM SPEED

MEDIUM LOW SPEED

LOW SPEED

4

5

3

2

1

4

3

2

1

5

*

Manufacturers Data

Model 300DCS

All units conform to
CSA and UL standards.

DIMENSIONS 300DCS

inches (mm

)

511 McCormick Blvd.

270 Regency Ridge,

Suite 210

London, Ontario N5W 4C8

Dayton, Ohio 45459

T (519) 457-1904

T (937) 439-6676

F (519) 457-1676

F (937) 439-6685

Email: [email protected] Website: www.lifebreath.com