Model 200max, Options, Performance – Lifebreath 95MAX User Manual

Page 7: Dimensions 200max, Engineering data

Advertising
background image

7

BALANCING DAMPER

33 5/8"

(850mm)

STALE AIR

FROM INSIDE

FRESH AIR

FROM OUTSIDE

STALE AIR

TO OUTSIDE

FRESH AIR

TO INSIDE

14 3/4"

(375)

19"

(483)

*All Duct Connections 6" (150mm)

CONDENSATE DRAINS

FILTERS

BLOWERS

*NOTE: Front clearance
of 25 inches (635 mm)
is recommended
for servicing unit.

RECIRCULATING

DEFROST

DAMPER

MOTOR

CORE

OPTIONS

99-104

Digital Electronic Timer - 20/40/60 min.

99-105

Programmable Ventilation Control (PVC)
includes Programmable Time Clock, Dehumidistat
and Air Sentry™

99-109

Air Sentry™ Air Quality Monitor designed to accept remotely
mounted Control Pad

99-250

Ventilation Dehumidistat - Dehumidistat designed to accept
remotely mounted Control Pad.

99-163

Duct Heater w/ Electronic SCR Thermostat, 1 Kw,
6” (150mm)

99-164

Duct Heater w/ Electronic SCR Thermostat, 2 Kw,
6” (150mm)

99-186

Weatherhoods, Two - 6” (150mm)
c/w 1/4” (6mm) mesh screen

WARRANTY Units carry a LIFETIME warranty on the heat recovery core
and a 5 year replacement parts warranty.

PERFORMANCE

HVI CERTIFIED

Net supply airflow in cfm (L/s) against external static pressure

E.S.P

cfm

L/s

@ 0.1” (25 Pa)

232

(109)

@ 0.2” (50 Pa)

223

(105)

@ 0.3” (75 Pa)

215

(102)

@ 0.4” (100 Pa)

195

(92)

@ 0.5” (125 Pa)

189

(89)

Maximum Temperature Recovery

81%

Sensible Effectiveness
@ 117 cfm (55 L/s)

(CSA C439M)

74%

Sensible Efficiency
@ 117 cfm (55 L/s) 32˚F (0˚C)

65%

Sensible Efficiency
@ 117 cfm (55 L/s) -13˚F (-25˚C) 66%

VAC @ 60HZ

120

WATTS / Low speed

87

WATTS / High speed

164

Amp rating

1.4

TI-99-NE

1203

200MAX FANCURVE

245

220

195

170

145

120

95

70

45

0.1

0.2

0.3

0.4

0.5

0.6

0.7

Air Flo

w

(cfm)

Static Pressure (inH

2

0)

5

4

3

2

1

HIGH SPEED

MEDIUM HIGH SPEED

MEDIUM SPEED

MEDIUM LOW SPEED

LOW SPEED

4

5

3

2

1

Model 200MAX

DIMENSIONS
200MAX

inches (mm

)

All units conform to
CSA and UL standards.

ENGINEERING DATA

THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two
airstreams. It is easily removed for cleaning or service.

MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC
motor. 5 speed fan operation. 120 VAC, 1.4 Amps.

FILTERS
Washable air filters in exhaust and supply air streams.

MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four rein-
forced polyester straps that are supplied with the unit.

DEFROST
Recirculating damper defrost system.

DEHUMIDISTAT
Adjustable Internal Dehumidistat.

CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion
resistance. Insulated to prevent exterior condensation.
Drain connections 2 - 1/2" (12 mm) OD.

CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, Recirculation
mode, (each mode has 5 speeds). Control pad can be removed from
HRV and remotely mounted.

WEIGHT 71 lbs. (32.5 kg SHIPPING WEIGHT 73 lbs. (33.5 kg)

511 McCormick Blvd.

270 Regency Ridge,

Suite 210

London, Ontario N5W 4C8

Dayton, Ohio 45459

T (519) 457-1904

T (937) 439-6676

F (519) 457-1676

F (937) 439-6685

Email: [email protected] Website: www.lifebreath.com

Advertising