Nortec NHTC User Manual

Page 120

Advertising
background image

10-30

Page 112

2008-10-01

Table 11. Controls – ON/OFF

Table 12. Modulating Control By NORTEC

Part No.

Description

Qty

2520259

DIGITAL HUMIDISTAT WALL MOUNTED ON/OFF
On/off wall mounted humidistat applicable as control humidistat or high limit
10% to 90% RH range with 5% non-adjustable differential.

Control ____

High Limit ____

2520273

DIGITAL HUMIDISTAT DUCT MOUNTED ON/OFF PACKAGE
On/off duct mounted humidistat, applicable as a control humidistat or high limit,
15% to 90% RH range with 4% non-adjustable differential.

Control ____

High Limit ____

132-9109

PRESSURE ELECTRIC SWITCH
On/off, remote mounted, 3 to 20 PSIG range, factory set to 13 PSIG with 2 to
6 PSIG fully adjustable differential, factory set to 3 PSIG. For use with
pneumatic humidistat (by others).

132-9203

AIR PROVING
On/off duct mounted, pressure differential switch, 0.07 IWC to 12.0 IWC fully
adjustable operating range, good for positive, negative or differential pressure
applications, stops humidifier if no differential pressure is sensed.

146-9000

COUPLED CIRCUITS
Factory internally wired in parallel to enable control of double circuit unit from
one set of external controls. Applies to NHTC 150 and 200 models only.

NOTE: NORTEC NH Series humidifiers must have a closed circuit across terminals 8 and 10. NORTEC highly

recommends the use of a high limit humidistat and air proving switch in series for this function.

Part No.

Description

Qty

2520266

DIGITAL WALL CONTROLLER WITH DUCT SENSOR PACKAGE
This is a digital LCD setpoint controller with a duct mounted humidity sensor
used for modulating high limit or control.

Control ____

High Limit ____

2520261

DIGITAL WALL CONTROLLER WITHOUT INTEGRAL SENSOR
This is a digital LCD setpoint controller to be used with one or all of the
following remote sensors: remote wall sensor, remote duct sensor and outdoor
duct mounted temperature sensor.

Control ____

High Limit ____

1510142

DIGITAL WALL CONTROLLER WITH INTEGRAL SENSOR
This is a digital LCD setpoint controller with a wall mounted humidity sensor
used for humidity control in the space.

Control ____

High Limit ____

2520263

OUTDOOR DUCT MOUNT TEMPERATURE SET BACK
This sensor can be mounted directly onto the fresh air intake of the ventilation
duct. The humidistat controller reads the outdoor temperature and resets the
humidity control setpoint to prevent condensation in windows or building
structures. Use with modulating controllers above.

1509857

REMOTE DUCT SENSOR
This humidity sensor can be mounted directly onto the return ventilation as the
main controlling sensor. It can also be used as a supply high limit sensor. It
must be used in conjunction with any other controller for remote sensing.

1509858

REMOTE WALL SENSOR
This humidity sensor can be mounted on a wall as the main controlling sensor.
It must be used in conjunction with any other controller for remote sensing.

Advertising