10-10

Page 29

2008-10-01

Table 9. Typical Absorption Distances, Single Distributor, 100 lbs/hr Humidifier

FPM

°F

°C

% RH

FT

CM

Typical System

(V)

(T)

(H)

(D)

500

70

21

30

3.0

91

Air handler before coils

500

55

13

80

4.5

137

Air handler after cooling

900

70

21

30

3.5

107

Supply air duct, on cool, no heat

900

55

13

70

6.0

183

Supply air duct, on cool

1000

55

13

90

8.0

244

Supply air duct, on cool with high humidity

1000

110

43

10

2.5

76

Supply air duct, on heating with low humidity

1000

70

21

45

4.0

123

Return air duct conditions

2000

55

13

45

10.0

305

Supply air duct higher pressure system

5000

140

60

10

2.0

61

After operating heating coil

(V) = Velocity at distributor location (T) = Temperature at distributor location
(D) = Absorption distance (visible steam) (H) = Humidity level after steam is absorbed

NOTE: This chart is for reference only; multiple distributors can reduce absorption distances.

Figure 3. Steam Distributor Location