(7) Vertical drop of the drip station should be 1.5 times the diameter of the steam main but

no less then 12".

(8) Install the P trap at the botom of the drip station. The P trap height is to be a minimum

of 6 inches or 2 “ greater than the static pressure in the duct.

(9) All distributors must be individually trapped.