Specifications, Output characteristics – National Instruments NI 9481E User Manual

Page 7

Advertising
background image

© National Instruments Corp.

7

NI 9481E Operating Instructions and Specifications

Specifications

The following specifications are typical for the range –40 to 85 °C
unless otherwise noted.

Output Characteristics

Number of channels.......................... 4 electromechanical relay

channels

Relay type ......................................... Single pole single throw

(SPST)

Power-on output state ....................... Channels off

Switching capacity (resistive load)

Switching voltage ....................... 60 VDC max, 250 V

rms

max

Switching current, per channel

One channel on .................... 4 A max at 30 VDC,

1 A max at 60 VDC,
4 A max at 250 V

rms

All channels on .................... 2 A max at 30 VDC,

1 A max at 60 VDC,
2 A max at 250 V

rms

Advertising