Appendix A

Specifications

NI ExpressCard MXI Series User Manual

A-6

ni.com

Environment

1

Maximum altitude...................................2,000 m (at 25 °C ambient

temperature)

Pollution Degree .....................................2

Indoor use only

Operating Environment

Module ambient temperature range ........0 to 65 °C (Tested in accordance

with IEC-60068-2-1 and
IEC-60068-2-2.)

Operating relative humidity....................5 to 95%, noncondensing

(Tested in accordance with
IEC-60068-2-56.)

Storage Environment

Ambient temperature range ....................–20 to 65 °C (Tested in

accordance with IEC-60068-2-1
and IEC-60068-2-2.)

Nonoperating thermal shock...................–20 to 65 °C, 5 shocks

Shock and Vibration

Nonoperating shock ................................50 g, 11 ms (Tested in accordance

with IEC 60068-2-27.)

Nonoperating vibration,
sinusoidal ................................................15 g 100 to 2000 Hz (Tested in

accordance with IEC 60068-2-6.)

Nonoperating drop test ...........................2 drops in 3 mutually exclusive

axes from 75 cm onto
no-cushioning vinyl tile surface

1

Specifications are subject to change without notice.