Top exit / horizontal termination, 90° h – Napoleon Fireplaces BGD38PT User Manual

Page 10

Advertising
background image

10

W415-0244 / A / 05.15.03

H

2

H

1

V

1

90°

when

(H

t

)

>

(V

t

)

Simple venting configuration (only one
90° elbow)

See graph to determine the required ver-
tical rise V

T

for the required horizontal

run H

T

.

V

1

=

V

T

= 6 ft

H

1

= 3 ft

H

2

= 5 ft

H

R

=

H

1

+

H

2

= 3 + 5 = 8 ft

H

O

= .03(two 90° elbows - 90°) = .03(180° - 90°) = 2.7 ft

H

T

=

H

R

+

H

O

= 8 + 2.7 = 10.7 ft

H

T

+ V

T

= 10.7 + 6 =16.7

Formula 1:

H

T

< 4.2 V

T

4.2 V

T

= 4.2 x 6 = 25.2 ft

10.7 < 25.2

Formula 2:

H

T

+ V

T

< 24.75 feet

16.7 < 24.75

Since both formulas are met, this vent configuration is ac-
ceptable.

For vent configurations requiring more than one 90° elbow
the following formulas apply:

Formula 1:

H

T

< 4.2

V

T

Formula 2: H

T

+ V

T

< 24.75 feet

Example 2:

Example 3:

V

1

= 4 ft

V

2

= 1.5 ft

V

T

=

V

1

+

V

2

= 4 + 1.5 = 5.5 ft

H

1

= 2 ft

H

2

= 1 ft

H

3

= 1 ft

H

4

= 1.5 ft

H

R

=

H

1

+

H

2

+

H

3

+

H

4

= 2 + 1 + 1 + 1. 5 = 5.5 ft

H

O

= .03(four 90° elbows - 90°) = .03(360° - 90°) = 8.1 ft

H

T

=

H

R

+

H

O

= 5.5 + 8.1 = 13.6 ft

H

T

+ V

T

= 13.6 + 5.5 = 19.1 ft

Formula 1:

H

T

< 4.2 V

T

4.2 V

T

= 4.2 x 5.5 = 23.1 ft

13.6 < 23.1

Formula 2:

H

T

+ V

T

< 24.75 feet

19.1 < 24.75

Since both formulas are met, this vent configuration is ac-
ceptable.

FIGURE 7

FIGURE 8

FIGURE 9

H

2

H

4

V

2

90°

H

3

H

1

V

1

90°

TOP EXIT / HORIZONTAL TERMINATION

REQUIRED
VERTICAL
RISE IN
INCHES

V

T

HORIZONTAL VENT RUN PLUS OFFSET IN FEET

H

T

The shaded area within the lines represents acceptable
values for H

T

and V

T

.

Advertising