Top exit vertical termination, 90° v, 90° h – Napoleon Fireplaces BGD38PT User Manual

Page 11

Advertising
background image

11

W415-0244 / A / 05.15.03

Example 4:

V

1

= 5 ft

V

2

= 10 ft

V

T

=

V

1

+

V

2

= 5 + 10 = 15 ft

H

1

= 1 ft

H

2

= 3 ft

H

3

= 2.5 ft

H

R

=

H

1

+

H

2

+

H

3

= 1 + 3 + 2.5 = 6.5 ft

H

O

= .03(four 90° elbows - 90°)

= .03(90 + 90 + 90 + 90 - 90) = 8.1 ft

H

T

=

H

R

+

H

O

= 6.5 + 8.1 = 14.6 ft

H

T

+ V

T

= 14.6 + 15 = 29.6 ft

Formula 1:

H

T

< V

T

14.6 < 15

Formula 2:

H

T

+ V

T

< 40 feet

29.6 < 40

Since both formulas are met, this vent configuration is ac-
ceptable.

when

(H

t

) < (V

t

)

Simple venting configurations

FIGURE 10

FIGURE 11

For vent configurations requiring elbows, the following for-
mulas apply:

Formula 1: H

T

< V

T

Formula 2: H

T

+ V

T

< 40 feet

See graph to determine the required vertical rise

V

T

for the

required horizontal run

H

T

.

90°

90°

90°

V

2

90°

H

1

V

1

H

3

H

2

REQUIRED
VERTICAL RISE
IN FEET

V

T

HORIZONTAL VENT RUN PLUS OFFSET IN FEET

H

T

The shaded area within the lines represents acceptable
values for H

T

and V

T

.

TOP EXIT VERTICAL TERMINATION