NI 9485 Operating Instructions

16

ni.com

Safety

Safety Voltages

Connect only voltages that are within these limits.

Channel a-to-Channel b .................... 60 VDC max, 30 V

rms

max

Isolation

Channel-to-channel

Continuous ........................... 60 VDC
Withstand ............................. 1,390 V

rms

, verified by a 5 s

dielectric withstand test

Channel-to-earth ground

Continuous ........................... 250 V

rms

,

Measurement Category II

Withstand ............................. 2,300 V

rms

, verified by a 5 s

dielectric withstand test

Measurement Category II is for measurements performed on
circuits directly connected to the electrical distribution system.
This category refers to local-level electrical distribution, such as
that provided by a standard wall outlet (for example, 115 V for U.S.
or 230 V for Europe). Do not connect to signals or use for
measurements within Measurement Categories III or IV.