Appendix a specifications, Specifications – National Instruments FP-1001 User Manual

Page 37

Advertising
background image

© National Instruments Corporation

A-1

FieldPoint FP-1000/FP-1001 User Manual

Appendix

A

Specifications

This appendix describes the specifications of the FP-1000 and FP-1001
network modules.

All FieldPoint network modules undergo extensive testing for operating
under rugged environmental conditions that exist in industrial
applications. FieldPoint network modules are designed and tested for
immunity and susceptibility, as well as for emissions.

Network

FP-1000 ..............................................1 RS-232 port, 1 RS-485

repeater port

FP-1001 ..............................................1 RS-485 port

Baud Rates ..........................................300, 1200, 2400, 9600, 19200,

38400, 57600, 115200
(switch settable)

Communication Parameters ................1 Start Bit, 8 Data Bits, 1 Stop

Bit, No Parity

Integrity ..............................................Checksum

Cabling Distance from Host*

FP-1000 .....................................50 ft (nominal)*

FP-1001 .....................................4000 ft (nominal)*

* Refer to the RS-232 Interface Specifications and RS-485 Interface
Specifications
sections in Chapter 2, Installation and
Configuration
.

Maximum Terminal Bases per Bank ...9

Maximum Number of Banks ...............25

RS-232/RS-485 Interface Chips ..........15 kV ESD, Low noise and Slew

rate interface ICs

Advertising