Nortec NH Series User Manual

Page 53

Advertising
background image

10-20

Page 46

2008-08-28

3. CONTROLS AND REMOTE COMMUNICATION (OPTIONAL)

A.

DIGITAL CONTROL OPERATION

(1) Figure 11 shows the components of the NORTEC Controller and how to adjust the

setpoint.

(2) In the case of a modulating NORTEC Controller, Figure 12 shows the relation between

the difference from setpoint to %rh in the room and the 0-10 V DC demand signal sent
out. From this basis the NORTEC Controller uses its PI algorithm to adjust its demand
signal in accordance with the history of the environment. This type of control allows for
tighter and more precise control.

B.

DIGITAL TRANSDUCER OPERATION

(1) The NORTEC digital transducers, shown in Figure 13, are designed to sense humidity

in duct or in room respectively, and report it back to a controller or the NHTC directly.
Required humidifier output is determined by controller or humidifier.

C.

REMOTE CONNECTIONS (OPTIONAL)

CAUTION

NORTEC DOES NOT RECOMMEND USING THE DRY RELAY
CONTACTS WITH ANYTHING MORE THAN 24 VAC, 1 AMP.

(1) The NHTC reports the signal light status, in Table 3, by closing the supplied dry contact

relays which can be wired back to a BMS or monitoring station. This method of
monitoring is not as informative as the actual display, but alerts you to the general
status of the unit.

Figure 11. NORTEC Digital Controller

Advertising