Nortec NH Series User Manual

Page 67

Advertising
background image

10-40

Page 60

2008-08-28

Table 3. NH System Messages

NHTC Display Message

LED state

System Action

Symptom Diagnosed

E5: Cylinder B Controller
missing

RED

Humidifier is in standby until
problem corrected.

On power up, the controller cannot
detect the driver board for cylinder B.

E6: Extendet Missing

RED

Humidifier activates its fault
relay and interrupts its operation
until communication is fixed.

The slave unit is not in communication
with the master unit. Master unit
powered?

E7: CPU CRC fault

RED

Humidifier activates its fault
relay and interrupts operation.

Problem with the processor hardware
or software.

W11: Safety Loop Open

GRN

Humidifier goes on standby.

ON/OFF controls wired between
terminal 1 and 2 are open.

W12: Cylinder Max Level

NONE

Fill valve interrupted.

Water at top of cylinder.

E12: Cylinder max Level no
current

RED

Humidifier activates its fault
relay and interrupts its
operation.

The high water sensor is activated but
no current is measured in cylinder.

W13: Fill Timeout

GRN
blink

The humidifier will attempt to
clear any debris by pulsing the
drain valve.

The fill valve has been activated for an
extended period of time but water has
not reached the sensor.

E13: Fill: Timeout

RED

The fill valve has been activated
for an extended period of time
but has not reached the sensor.

Humidifier stops operation and the
fault relay is activated.

W15: Over current

YEL

The drain is activated to
decrease the water level in the
cylinder.

Measured current in the cylinder has
exceeded 115% of rated output.

E15: Over Current

RED

Humidifier interrupts operation
and the fault relay is activated.

Measured current in the cylinder has
exceeded 115% of rated output.

W16: Excess Current

YEL

Humidifier interrupts operation
and the fault relay is activated.

Measured current in the cylinder has
exceeded 115% of rated output.

E16: Excess Current

RED

Humidifier interrupts operation
and the fault relay is activated.

Measured current in the cylinder has
exceeded 130% of rated output.

Advertising