background image

10-50

Page 68

2008-08-28

1. WIRING AND TERMINALS

A.

HUMIDIFIER CONTROL INFORMATION

(1) See Figure 7 and Figure 9 in Chapter 10-10 for Controller and Transducer terminal

definitions. See Figure 6 in Chapter 10-10 for low voltage terminal strip terminal
definitions.

Table 1. Controller and Sensor Specifications

Power Supply

Operating Voltage

24 VAC ± 10%
50/60 Hz

Power Consumption

Max. 3 VA

Internal Rectification

Half-wave rectified

Signal Inputs

Analog Input
Input Signal
Resolution
Accuracy

AI1
2-10 VDC
39 mV, 0.078 mA

± 2%

Temperature Input
Range

External Thermistor
-40° to 140°C (-40° to 284°F)

Humidity Input:
Range
Accuracy
Repeatability

0 to 100 %RH

± 3.0% at 25°C (77°F)

± 0.5%

Signal Outputs

Digital Outputs
Maximum Load

DO1
24 VAC 2A max.

Environment

Operation
Temperature
Humidity

0° to 50°C(32° to 122°F)
<95%RH

Housing Materials

Cover, back
Mounting Plate

Fire proof ABS plastic
Galvanized Steel