(2) WIRING

(A) BACNET/MSTP, JOHNSON N2, AND LONWORKS

(1) The necessary internal wiring for the Gateway is already present except for the BMS

network connection that can be made via twisted-pair at terminals A and B. To
network multiple units to a single Gateway, the units may be daisy-chained to each
other using the network link terminals at the TB3 connection jack on the humidifier
logic board. Refer to wiring diagram in section 10-50.

(1) Table #1 refers to the recommended wire types and maximum recommended

lengths from the Nortec LINK 2 module to the front-end of the Building Management
system. Since communication between the humidifiers and Nortec Links will always
occur via a EIA-485 signal type, Nortec recommends using a 18-24 AWG shielded,
twisted pair wire between the lead humidifier and each of the slave humidifiers.
Cable runs between the Nortec LINKS 2 module and the furthest slave humidifier
should not exceed 2,000 feet. Signal boosters or repeaters may be necessary for
longer wire runs or where electrical noise interference is prevalent.

Table 1. Recommended Wire Types and Lengths

Polarity

Protocol

Signal

Type

A

B

Recommended

Cable

Maximum

Recommended

Distance from Nortec

Module

BACnet
MS/TP
Johnson N2

EIA-485,

2-wire

Net +

Net -

18-24 AWG

Shielded, Twisted

Pair

2300 ft at 9.600 kbps

2000 ft at 38,400 kbps

BACnet/IP

LAN

standard

N/A N/A

CAT.5E cable with

RJ-45 termination

Depends on cable

manufacturer

LonWorks

EIA-232,

2-wire

Tx

Rx

18-24 AWG

Twisted Pair

Should not exceed 50 ft.

(B) BACNET/IP

(1) The necessary wiring for the Gateway is present except for the network cable,

which must be connected to the RJ-45 (Ethernet) jack on the Gateway. Refer to
wiring diagram in section 10-50.