Table 3. Variable Definitions

Variable Name

R=Read

W=Write

Description LonWorks

SNVT

nvoHourOpt_x

R

Analogue Value

Indicates the number of hours the

humidifier cylinder has been in

operation.

SNVT_count_inc

nvoCapLimit

R

Analogue Value

Reads to capacity limitation

applied to the unit output.

(50-100%)

SNVT_switch

nvoRHDem1_x

R

Analogue Value

Reads Ch.1 input signal in %RH

or demand to humidifier.

(0-100%)

SNVT_switch

nvoSet1_x

R

Analogue Value

Reads Ch.1 setpoint setting.

(10-90%)

SNVT_switch

nvoRHDem2_x

R

Analogue Value

Reads Ch.2 input signal in %RH

or demand to humidifier.

(0-100%)

Unit must be configured for dual

channel operation.

SNVT_switch

nvoSet2_x

R

Analogue Value

Reads Ch.2 setpoint setting.

(10-90%)

Unit must be configured for dual

channel operation.

SNVT_switch

nvoSysDemand_x

R

Analogue Value

Reads humidifier system

demand. (0-100%)

SNVT_switch

nviCapLimit

R

Analogue Value

Sets the humidifier’s unit

capacity. (50-100%)

nviRHDem1_x

W

Analogue Value

Writes Ch.1 demand or %RH

level. Allows BMS control of

humidifier output. (0-100%)

Unit must be configured for

networked demand

SNVT_switch

nviRHDem2_x

W

Analogue Value

Writes Ch.2 demand or %RH

level. Allows BMS control of

humidifier output. (0-100%)

Unit must be configured for

networked demand

SNVT_switch

nviSet1_x

W

Analogue Value

Writes Ch.1 setpoint (0-90%)

SNVT_switch

nviSet2_x

W

Analogue Value

Writes Ch.2 setpoint (0-90%)

SNVT_switch