Variable Name

R=Read

W=Write

Description LonWorks

SNVT

nvoFault_x

R

Binary Value

Indicates unit fault status.

0=no fault, 1=fault.

SNVT_switch

nvoHWSensor_x

R

Binary Value

Indicates if a high-water level

condition exists in the humidifier

cylinder.

0=normal, 1=high water condition

nvoNetSensor_x

R

Binary Value

Reads configuration status for

network-enabled sensing or

control.

0=%RH or %demand input is not

from the network

1=%RH or %demand input is from

the network

SNVT_switch

nvoDisable_x

R

Binary Value

Reads remote disable status.

0=humidifier enabled,

1=humidifier disabled by network

SNVT_switch

nvoSecurity_x

R

Binary

Indicates security loop status.

0=Sec. loop open,

1=Sec. loop closed

SNVT_switch

nvoService_x

R

Binary Value

Reads service requirement status.

0=no service required,

1=service required

SNVT_switch

nvoStatus_x

R

Binary Value

Reads humidifier status.

0=standby, 1=humidifying.

SNVT_switch

nvoConnection_x

R

Binary Value

Indicates that the Nortec Links

module is communicating with the

Humidifier

SNVT_switch

nviDisable_x

W

Binary Value

Writes remote disable status.

0=humidifier enabled,

1=humidifier disabled from

network

SNVT_switch

nviNetSensor _x

W

Binary Value

Writes configuration status for

network-enabled sensing or

control.

0=%RH or %demand input is not

from the network

1=%RH or %demand input is from

the network

SNVT_switch