Nhtc – Nortec Industries NHTC Series User Manual

Page 24

Advertising
background image

10-10

Page 17
2008-02-18


















Figure 3. Sample Humidification Applications

Room-Sensed %RH Feedback with Duct Hi-Limit Sensing (0-10V Signal Directly to

Humidifier)

nviDisable_x = 1 Unit Disabled

= 0 Unit Enabled

Configuration Variables
nviInputType_x = 1
nviNetSensor_x = 0

Control Variables
nviSet1_x = Room Setpoint (0-100%)
nviSet2_x = Hi-Limit Setpoint (0-100%)
nviRHDem1_x = Room %RH

(0-100%)

nviRHDem2_x = Hi-Limit %RH

(0-100%)

Readable Variables
nvoStatus_x = 1 Humidifying

= 0 Standby

nvoService_x = 1 Service Required

= 0 No Service Required

nvoFault_x = 1 Fault

= 0 No Fault

nvoSysDemand_x = System Demand(0-100%)
nvoDisable_x = 1 Unit Disabled

= 0 Unit Enabled

NHTC