1.1.4 Setting the capacity limitation

Select “Power Limit” in the settings menu,
then press the <Set> key. In the upcoming
modification dialogue set the desired capacity
limitation in % of the maximum capacity of the
humidifier.

Factory setting:
100 %
Setting range:
30...100 %


1.1.5 Configuring the supply pipe flushing

Select “Inlet Flush” in the settings menu, then
press the <Set> key.

Used to configure the unit to flush supply lines
even if there is no demand signal. You can;
- enable / disable inlet flush
- set length of flush
- set time between flushes

DESCRIPTION OF THE SETTINGS
Inlet Flush

Enable or disable the supply pipe flushing.

Factory setting: On
Options:

On (enable)

Off

(disable)

Drain Time

Setting the flushing time in seconds.

Factory setting:
60s
Setting range:

5...600s

Periodic Int

Setting the time without demand after which
the supply pipe should be flushed.

Factory setting: 12.0 h
Setting range:

0.5 ... 24.0 h