Nortec MH Series User Manual
Page 18
10-10
Page 14
2008-12-03
.
1.1.4 Setting the capacity limitation
Select “Power Limit” in the settings menu,
then press the <Set> key. In the upcoming
modification dialogue set the desired capacity
limitation in % of the maximum capacity of the
humidifier.
Factory setting: 100 %
Setting range: 30...100 %
1.1.5 Configuring the supply pipe flushing
Select “Inlet Flush” in the settings menu, then
press the <Set> key.
Used to configure the unit to flush supply lines
even if there is no demand signal. You can;
- enable / disable inlet flush
- set length of flush
- set time between flushes
DESCRIPTION OF THE SETTINGS
Inlet Flush
Enable or disable the supply pipe flushing.
Factory setting: On
Options:
On (enable)
Off
(disable)
Drain Time
Setting the flushing time in seconds.
Factory setting: 60s
Setting range:
5...600s
Periodic Int
Setting the time without demand after which
the supply pipe should be flushed.
Factory setting: 12.0 h
Setting range:
0.5 ... 24.0 h