• When equipped with two HI voltage power supplies, independent AC sources can be

used to power the product for greater redundancy.

2.2.2. DC Power Supply Wiring Examples

+

Figure 2.6. DC Single Power

Supply Wiring Example

+

+

Figure 2.7. DC Dual Redundant

Power Supply Wiring Example

• 88-300 VDC rated equipment: A 300 VDC appropriately rated circuit breaker must be

installed.

• A circuit breaker is not required for 12, 24 or 48 VDC rated power supplies.

• For dual DC power supplies, Separate circuit breakers must be installed and separately

identified.

• Equipment must be installed according to the applicable country wiring codes.