Ieee 1613 type tests, Military standard tests, 25 4.3. military standard tests – RuggedCom M2100 User Manual
Page 25

4. Type Tests
RuggedCom® RuggedSwitch®
25
M2100 Installation Guide Rev 1.0
Test
Description
Test Levels
Severity
Levels
AC Power ports
2 kVAC
N/A
Signal ports
5 kV (Fail-Safe Relay output)
N/A
DC Power ports
5 kV
N/A
IEC 60255-5
H.V. Impulse
AC Power ports
5 kV
N/A
Table 4.1. IEC 61850-3 Type Tests
4.2. IEEE 1613 Type Tests
Test
Description
Test Levels
Enclosure Contact
± 8 kV
IEEE C37.90.3
ESD
Enclosure Air
± 15 kV
IEEE C37.90.2
Radiated RFI
Enclosure ports
35 V/m
Signal ports
± 4 kV @ 2.5 kHz
DC Power ports
± 4 kV
AC Power ports
± 4 kV
IEEE C37.90.1
Fast Transient
Earth ground ports
± 4 kV
Signal ports
2.5 kV common mode @ 1 MHz
DC Power ports
2.5 kV common, 1 kV
diff. mode @ 1 MHz
IEEE C37.90.1
Oscillatory
AC Power ports
2.5 kV common, 1 kV
diff. mode @ 1 MHz
Signal ports
5 kV (Fail-Safe Relay output)
DC Power ports
5 kV
IEEE C37.90
H.V. Impulse
AC Power ports
5 kV
Signal ports
2 kVAC
DC Power ports
1.5 kVDC
IEEE C37.90
Dielectric Strength
AC Power ports
2 kVAC
Table 4.2. IEEE 1613 Type Tests
4.3. Military Standard Tests
Test
Description
Test Levels
MIL-STD-901D
Shock (Hard-Mounted)
Grade A, Equipment Class
I, Shock Type A Equipment
MIL-STD-167-1
Vibration
Type I (Upper Frequency of 33 Hz)